48NDT
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-9444-A Rev.9 P. 6 / 8
ADJUSTMENT PROCEDURE
L
SET
L
M
Increase / Decrease
L Setpoint
Complete
LL
SET
LL
M
Increase / Decrease
LL Setpoint
Complete
H
M
Press at once
ON Time Delay for
H Setpoint
Increase / Decrease
Complete
Digital Indicator
H
SET
H
M
Increase / Decrease
H Setpoint
Complete
HH
SET
HH
M
Increase / Decrease
HH Setpont
Complete
2
SET
2
M
Increase / Decrease
Increase / Decrease
Setpoint 2
Complete
1
SET
1
M
Setpoint 1
Complete
LED OFF
LED OFF
LED Blinking
Mode Selector
*
1
UP / DOWN Button
UP / DOWN Button
LED Blinking
Mode Selector
*
1
UP / DOWN Button
LED Blinking
Mode Selector
*
1
UP / DOWN Button
LED Blinking
Mode Selector
*
1
■
ZERO ADJUSTMENT
: Apply 0% input signal before adjustment. All alarm setpoints will be reset after the adjustment.
SET
H
HH
M
Press at once
ON Time Delay for
HH Setpoint
Increase / Decrease
Complete
Digital Indicator
SET
HH
L
M
Press at once
ON Time Delay for
L Setpoint
Increase / Decrease
Complete
Digital Indicator
SET
L
LL
M
Press at once
ON Time Delay for
LL Setpoint
Increase / Decrease
Complete
Digital Indicator
SET
LL
Z
M
Press at once
Zero Adjustment
Digital Indicator / Bargraph
Z
SET
Z
M
Increase / Decrease
Zero Adjustment
Digital Indicator Only
Complete
Z
ON
LED OFF
■
SPAN ADJUSTMENT
: Apply 100% input signal before adjustment. All alarm setpoints will be reset after the adjustment.
S
LED OFF
■
DECIMAL POINT POSITION
■
ALARM SETTING
: Proceed after the zero / span adjustments and the decimal point position setting.
• 48NDT-4, 48NDT-2
*
2
• 48NDT-0
*
3
*
1. Keep pressing at least for 3 seconds to activate Mode Selector M. Press briefly for second and more times within 1 minute after it has been activated.
*
2. HH or LL setpoints are not provided for the 48NDT-2.
*
3. 1 or 2 setpoints are not provided for the 48NDT-0R, -0Y, -0G or -0B.
Note: Each setting sequence is complete only when SET button is pressed. Once set, parameters are not lost even after the power is removed.
M
Press at once
Span Adjustment
Digital Indicator / Bargraph
S
SET
S
M
Increase / Decrease
Span Adjustment
Digital Indicator Only
Complete
S
ON
P
SET
M
Increase / Decrease
Decimal Point Position
Complete
P