P. 2 / 5

EM-955-B Rev.2

PARAMETER

Alarm points

Quad alarm: LL, L, H, HH

Dual alarm: L, H

INDICATORS

FUNCTION

DEFAULT

VALUE

DISPLAY

L

H

Fnc

L

H

HH

LL Fnc

...

...
...

LL setpoint

LL deadband (hysteresis) 
LL ON delay time

LL: ON delay time (seconds)

LL: Deadband (hysteresis) value

LL: Setpoint value

LL Fnc

LL trip action

LL: Hi trip

LL Fnc

LL: Lo trip

LL coil at alarm

LL: Coil energized at alarm

LL Fnc

LL: Coil de-energized at alarm

LL alarm tone

LL: Alarm tone OFF

LL Fnc

LL: Alarm tone ON

L alarm tone

L: Alarm tone OFF

L

Fnc

L: Alarm tone ON

H alarm tone

H: Alarm tone OFF

H

Fnc

H: Alarm tone ON

HH alarm tone

HH: Alarm tone OFF

HH Fnc

HH: Alarm tone ON

D/P

LL

Fnc

LL

P

Fnc

...

...
...

L setpoint

L deadband (hysteresis) 
L ON delay time

L: ON delay time (seconds)

L: Deadband (hysteresis) value

L: Setpoint value

L

Fnc

L trip action

L: Hi trip

L

Fnc

L: Lo trip

L coil at alarm

L: Coil energized at alarm

L

Fnc

L: Coil de-energized at alarm

D/P

L

Fnc

L

P

Fnc

...

...
...

H setpoint

H deadband (hysteresis) 
H ON delay time

H: ON delay time (seconds)

H: Deadband (hysteresis) value

H: Setpoint value

H

Fnc

H trip action

H: Hi trip

H

Fnc

H: Lo trip

H coil at alarm

H: Coil energized at alarm

H

Fnc

H: Coil de-energized at alarm

D/P

H

Fnc

H

P

Fnc

...

...
...

HH setpoint

HH deadband (hysteresis) 
HH ON delay time

HH: ON delay time (seconds)

HH: Deadband (hysteresis) value

HH: Setpoint value

HH Fnc

HH trip action

HH: Hi trip

HH Fnc

HH: Lo trip

HH coil at alarm

HH: Coil energized at alarm

HH Fnc

HH: Coil de-energized at alarm

D/P

HH

Fnc

HH

P

Fnc

Note 1: Alarm Setting Mode is locked with no-alarm-output type.

 

Alarm points depend upon the model suffix code.  LL and HH setpoints are usable only for quad alarm type.

Note 2: LED status:           = ON,          = Blinking

Note 3: Specify setpoint and deadband in the scaled range values.  Alarm is disabled when ‘ – – – – ’ is specified for the setpoint.

Note 4: All alarm setpoints are disabled (reset to ‘ – – – – ’ status) when the input type has been changed.  Re-setting is required.

Note 5: Decimal point is not indicated when setting deadband values.

Main display flashing 

at alarm

Flashing in 1.0 sec. intervals

No flashing

Fnc

Flashing in 0.1 sec. intervals

Flashing in 0.2 sec. intervals

Flashing in 0.5 sec. intervals

Содержание 47LPA

Страница 1: ...erly indicate it POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 100 240V AC rating 85 264V 50 60 Hz appro...

Страница 2: ...the H alarm is tripped HH turns on when the HH alarm is tripped P turns on when none of the other alarms is tripped 3 Function indicators Indicate the device status 4 Max Min button Used to switch th...

Страница 3: ...2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 20 M3 SCREW TERMINAL 2 M3 SCREW 10 M3 SCREW TERMINAL INSTALLATION HOW TO MOUNT THE UNIT ON A PANEL The watertight packing must be in place to hold the...

Страница 4: ...lar devices to the input terminals to eliminate the input signals instability 8V 5k COM 3 4 5 1 2 Short EXC OC JP INP COM DI SENSOR EXCITATION INPUT CONTROL INPUT SHORT CIRCUIT EXC OC JP INP COM DI SE...

Страница 5: ...ut Setting Mode Go through the lockout settings Measuring Mode Hold down Alarm or Scale button for 1 second Hold down Scale button for 3 seconds Measuring Measuring stopped 3 Mode transition 1 Preset...

Страница 6: ...e button shifts one to the previous Changing parameters Pressing Shift button while one of the parameter settings is indicated on the display shifts the panel meter into the setting standby mode The d...

Страница 7: ...0000 Hold down Scale button for 3 seconds Hold down Alarm or Scale button for 1 second Shift Shift Alarm Scale Alarm Alarm Scale Alarm Alarm Scale Alarm Scale Alarm Shift Shift Alarm Scale Alarm Scal...

Страница 8: ...frequency for F10K F0 1M 120 kHz Note 2 Turn off the input signal while changing the input type 4 positions or none Decimal point position Display value for Input Scaling Value B Input value for Full...

Страница 9: ...he desired output value Analog output 0 5 Analog output 100 Analog output function mode Proportional to the display value Fnc Zro Spn Fnc Proportional to the scaling value Analog output 0 adjustment A...

Страница 10: ...d L ON Delay Time 19999 19999 0000 9999 00 99 Shift Shift Alarm Alarm Alarm Alarm Alarm Alarm L Coil at Alarm RYEN RYDN Shift Alarm Alarm Shift L Trip Action LMHI LMLO Alarm Alarm LL Coil at Alarm RYE...

Страница 11: ...Alarm HH Coil at Alarm RYEN RYDN Shift Alarm Alarm Shift HH Setpoint 19999 19999 Shift H Setpoint H Deadband H ON Delay Time 19999 19999 0000 9999 00 99 Shift Shift Alarm Alarm Alarm Alarm Alarm Alarm...

Страница 12: ...me H ON delay time seconds H Deadband hysteresis value H Setpoint value H Fnc H trip action H Hi trip H Fnc H Lo trip H coil at alarm H Coil energized at alarm H Fnc H Coil de energized at alarm D P H...

Страница 13: ...e scaled range disregarding the decimal point With the cutout set to OFF the low end cutout value setting is locked Automatic return time to Measuring Mode The display goes back automatically to Measu...

Страница 14: ...1 Preset time can be specified with Transition Time to Lockout Setting Mode in Advanced Setting Mode A Scale Scale Scale Scale Scale Set value Setting Parameters A Alarm Alarm PARAMETER Alarm setting...

Страница 15: ...r reading Non volatile memory error writing 1 All parameter settings are reset to the factory default values If the unit does not recover its function after the initialization repairing in the factory...

Отзывы: