background image

3/6

WIRING

  1.

  

The LED-BP-SLIM-XX Series requires an unswitched AC power supply of 120-277 volt, 

       50/60Hz.
  2.  The LED-BP-SLIM-XX Series and AC driver must be on the same branch circult. Ensure 
       the output current of the AC driver does not exceed 3A.
  3.  Refer the wiring diagrams below for wiring. Consult the factory for other wiring diagrams.  

FOR AC LED TUBE/BULB/LUMINAIRE 

FOR DC LED LOAD 

N

L IN

L OUT

LED Test Switch

Red(+)

White(-)

LED DRIVER

N

L

Red(+)

White(-)

LED Test Switch

  LED LOAD

LED(-)

LED(+)

Red/Blue
Blue

White/Red

Blue/White

Input

Output 

Output 

Gray

White/Black

Green/Yellow

Switch

Black

White/Black

HOT

Common

GND

LINEAR EMERGENCY 
EQUIPMENT 

Green/Yellow

N

L IN

L OUT

LED Test Switch

Red(+)

White(-)

LED Test Switch

N

L

Red/Blue

Blue

White/Red

Blue/White

AC LED TUBE/BULB
/LUMINAIRE

Input

Output 

Gray

Switch

Black

White/Black

HOT

White/Black

Common

GND

Red(+)

White(-)

LINEAR EMERGENCY 
EQUIPMENT 

            1-800-982-4587
www.lvscontrols.com

Содержание LED-BP-SLIM Series

Страница 1: ...tlets or other hazardous location 8 Use this product in 0 C minimum 55 C maximum ambient temperatures Ta 9 Do not attempt to service the batteries A sealed non maintenance battery is used that is not field replaceable Contact the manufacturer for information or service 10 The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition and void warranty 11 Do not use...

Страница 2: ...fter installation Drill a 1 2 12 mm hole for mounting the LTS Connect the wires from LTS to the LED BP SLIM model according to the wiring diagram on page 3 INSIDE THE LUMINAIRE LED test switch LED BP SLIM XX TB LED BP SLIM MODEL SPECIFICATIONS MODEL EMERGENCY OUTPUT CONSTANT 4 5 WATTS 13 5 WATTS LED BP SLIM 4 5W LED BP SLIM 4 5W TB VOLTAGE OUTPUT 5 200 VDC 15 300 VDC LED BP SLIM 9W LED BP SLIM 9W ...

Страница 3: ...LUMINAIRE FOR DC LED LOAD N L L IN L OUT LED Test Switch Red White LED DRIVER N L Red White LED Test Switch LED LOAD LED LED Red Blue Blue White Red Blue White Input Output Output Gray White Black Green Yellow Switch Black White Black HOT Common GND LINEAR EMERGENCY EQUIPMENT Green Yellow N L L IN L OUT LED Test Switch Red White LED Test Switch N L Red Blue Blue White Red Blue White AC LED TUBE BU...

Страница 4: ...es out 1 800 982 4587 www lvscontrols com LED BP SLIM 4 5W TB LED BP SLIM 9W TB Item No L1 mm inch 200 7 87 W mm inch H mm inch 260 10 24 345 13 58 410 16 14 190 7 48 250 9 84 335 13 19 400 15 70 30 1 18 22 0 87 30 1 18 22 0 87 30 1 18 22 0 87 30 1 18 22 0 87 M Mounting mm inch LED BP SLIM 13 5W TB LED BP SLIM 18W TB Dimension unit mm inch LED BP SLIM 4 5W LED BP SLIM 9W Item No L1 mm inch 258 10 ...

Страница 5: ...ys after initial power on Then monthly tests will be performed every 30 days b Annual Auto test will occur every 52 weeks after initial power on Monthly Auto Test The Monthly Auto Test shall be executed every 30 days and will test Normal to emergency transfer function emergency charging and discharging conditions are normal Monthly test time is approximately 30 60 seconds Annual Auto Test Annual A...

Страница 6: ...uminaire Lumens per Watt efficacy in Rated Data specifications F Multiply luminaire Lumens per Watt by Emergency rated output of the ELBP XX S series Refer to the table below 3 Determine Suitability of Means of Egress Lighting Levels Using industry standard lighting design software with the IES files for the emergency luminaires verify that the above calculated emergency lumens are sufficient to meet ...

Отзывы: