5/6
OPERATION / TESTING / MAINTENANCE
O
PERATION
When AC ower is appli d, the LED test switch is illuminated indicating that the batteri s are being
p
e
e
,
charged. When
C power fails, the LED-BP-SLIM Series automatically switches to emergency power
A
,
operating
the
lighting
load
at
rated
emergency
power
.
During power
failure, the LED
test
switch
will
be
off
.
When
the
AC
power
is
restored
,
the
emergency
LED-BP-SLIM Series
switches
the
system
back to
normal mode
of
operation
and resumes battery charging. The minimum emergency
operation time is 90 minutes. The charging time for a full discharge is 24 hours
.
TESTING AND MAINTENANCE
The following Periodic testing is recommended to ensure the system is working correctly.
1. Visually inspect the LED test switch (LTS) monthly. It should be illuminated when AC power is applied.
2. Conduct a 30-second discharge test by switching off the emergency breaker every month. The LTS will
be off.
3. Conduct a 90-minute discharge test once per year. The LTS will be off during test.
AUTO TEST
The
LED-BP-SLIM Series has an Auto Test feature which saves cost by reducing the need for manual
testing
.
1. Initial Auto Test
When the system is connected properly an
d powered on, the
w
LED-BP-Slim Series
ill perform an initial
Auto Test
.
If any
abnormal
conditions exist, the LTS will blink qui
ckly. Once
the
abnormal
condition is
corrected, the LTS
will
function
correctly
.
2. Preprogrammed Scheduled Auto Test
a) The unit will conduct the first Monthly Auto Test after 24 hours and up to 7 days after initial power
on
.
Then
monthly
tests will be performed every 30 days.
b) Annual Auto test will occur every 52 weeks after initial power on.
- Monthly Auto Test
The Monthly Auto Test shall be exe
cuted every 30 days, and will test;
Normal
to
e
mergency tra
nsfer function, emergency, charging
and
discharging
conditions
are
normal
.
Monthly
test time is approximately 30
~
60 seco
nds.
- Annual Auto Test
Annual Auto Test will
occur every 52 weeks
after
the initial 24
hours
full charge, and will
test
;
P
roper initial battery vol
tage
,
90-minute
emergency
operation
and
acceptable
battery
voltage
at the
end
of the
full
90-minute
test
.
If the Auto Test is interrupted by a power failure, a full 90-minute Auto Test will occur again 24 hours after
the power is restored.If the power failure causes the battery to fully discharge, the product will restart
the Initial Auto Test and Preprogrammed Scheduled Auto Test.
MANUAL TEST
- Press the LTS one time to simulate emergency mode.
- Press the LTS 2 times continuously within 5 seconds to force a monthly test
.
After the test is completed,
the next (30-day) monthly test will count from this date.
- Press the LTS 3 times continuously within 5 seconds to force a annual test. After the
test is complete
d
,
the next
(52-week)
annual test will count from this date.
- During any manual test, press and hold the LTS for greater than 3 seconds to terminate a manual test
.
The
P
reprogramm
ed Scheduled Auto Test time will not change
.
LED TEST SWITCH CONDITIONS
LTS Slow Blinking: Normal Charging
LTS On: Battery Fully Charged - Normal Condition
LTS Off: Power Failure
LTS Gradual Change: In Testing Mode
LTS Quickly Blinking: Abnormal Condition - Corrective
Action
Required