700678-LTG-E-0415
Johnson Controls Unitary Products
21
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCJD36S4(3,4)S3(E)
INDOOR COIL MODEL NO.
FC/MC/PC37
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
ID CFM
1000
1200
1400
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
35.3
37.4
37.0
39.3
40.4
36.3
38.1
37.4
39.7
40.2
37.3
38.8
37.8
40.1
40.1
S.C.
33.1
29.8
25.3
24.2
18.1
34.1
31.8
26.8
25.2
18.5
35.2
33.8
28.3
26.1
18.9
KW
2.40
2.42
2.41
2.44
2.44
2.49
2.50
2.50
2.53
2.53
2.58
2.58
2.60
2.61
2.63
75
T.C.
33.8
35.6
35.1
37.7
39.3
34.9
36.4
35.6
38.1
39.3
36.1
37.2
36.1
38.5
39.3
S.C.
31.7
29.4
24.8
23.9
17.9
32.9
31.4
26.5
25.1
18.5
34.1
33.3
28.2
26.3
19.1
KW
2.61
2.63
2.62
2.66
2.67
2.71
2.72
2.71
2.75
2.77
2.80
2.80
2.80
2.83
2.86
85
T.C.
32.4
33.8
33.3
36.2
38.1
33.6
34.7
33.8
36.6
38.3
34.8
35.6
34.4
37.0
38.4
S.C.
30.4
29.0
24.3
23.5
17.7
31.7
30.9
26.1
25.0
18.5
33.0
32.8
28.0
26.5
19.3
KW
2.82
2.84
2.84
2.88
2.91
2.92
2.93
2.92
2.96
3.00
3.02
3.03
3.01
3.05
3.09
95
T.C.
31.0
32.0
31.5
34.6
37.0
32.3
33.0
32.1
35.0
37.3
33.6
34.0
32.7
35.4
37.6
S.C.
29.0
28.6
23.7
23.1
17.5
30.5
30.5
25.8
24.9
18.5
31.9
32.3
27.9
26.6
19.5
KW
3.04
3.05
3.05
3.09
3.14
3.14
3.15
3.13
3.18
3.23
3.24
3.25
3.22
3.27
3.32
105
T.C.
28.0
28.9
27.8
31.1
34.3
28.9
29.9
28.5
31.6
34.6
29.9
30.9
29.2
32.0
34.9
S.C.
26.3
26.2
22.0
21.9
16.6
27.4
27.8
23.8
23.8
17.7
28.5
29.4
25.6
25.7
18.9
KW
3.25
3.25
3.23
3.30
3.37
3.36
3.36
3.33
3.39
3.47
3.47
3.47
3.43
3.49
3.56
115
T.C.
25.0
25.9
24.3
27.8
31.7
25.7
26.9
25.1
28.2
32.0
26.4
27.9
25.9
28.7
32.3
S.C.
23.7
23.9
20.3
20.8
15.8
24.4
25.2
21.8
22.8
17.0
25.2
26.6
23.4
24.7
18.3
KW
3.45
3.46
3.42
3.50
3.60
3.57
3.57
3.52
3.60
3.70
3.68
3.69
3.63
3.70
3.79
125
T.C.
22.1
22.9
20.7
24.4
29.0
22.5
23.9
21.7
24.9
29.3
22.9
24.9
22.6
25.4
29.6
S.C.
21.1
21.5
18.6
19.7
15.0
21.5
22.7
19.9
21.7
16.3
21.9
23.8
21.1
23.8
17.7
KW
3.65
3.66
3.60
3.70
3.83
3.78
3.78
3.71
3.80
3.93
3.90
3.91
3.83
3.91
4.03
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC37
1.00
1.00
1.00
–
FC/MC/PC43
1.00
1.00
1.00
–
FC/MC/PC48
1.00
1.00
1.00
–
UC48
1.00
1.00
1.00
AHE36C
–
1.02
1.02
0.93
AHE42D
–
1.02
1.04
0.92
AHR36B
–
0.99
0.99
0.99
AHR42C
–
1.02
1.02
0.99
AHV36C
–
1.02
1.04
0.94
AHV42D
–
1.03
1.04
0.92
AHV48D
–
1.02
1.02
0.91
MV12B
FC/MC43B
1.01
1.02
0.95
MV12D
FC/MC48D
1.00
1.02
0.92
MV16C
FC/MC43C
1.03
1.02
0.94
MV16C
FC/MC48C
1.03
1.02
0.94
MV20D
FC/MC48D
1.03
1.03
0.94
MX12BN21
FC/MC43B
1.00
0.99
0.92
MX12DN21
FC/MC48D
1.01
1.02
0.89
MX16CN21
FC/MC43C
1.01
1.03
0.91
MX16CN21
FC/MC48C
1.02
1.04
0.91
MX20DN21
FC/MC48D
1.03
1.05
0.89
Furnaces
Coils
T.C.
S.C.
KW
T*(8,L)V*A12
FC/MC/PC37A
0.97
0.93
0.97
T*(8,L)V*B12
FC/MC/PC43B
1.01
1.02
1.01
T*(8,L)V*C16
FC/MC/PC43C
1.02
1.02
0.97
T*(8,L)V*C16
FC/MC/PC48C
1.03
1.05
0.94
T*(8,L)V*C16
UC48C
0.99
1.00
0.95
T*(8,L)V*C20
FC/MC/PC43C
1.02
1.02
0.93
T*(8,L)V*C20
FC/MC/PC48C
1.03
1.05
0.94
T*(8,L)V*C20
UC48C
0.99
1.00
0.95
T*9(C,V)*B12
FC/MC/PC43B
1.01
1.02
1.01
T*9(C,V)*C16
FC/MC/PC43C
1.01
1.02
0.97
T*9(C,V)*C16
FC/MC/PC48C
1.03
1.05
0.98
T*9(C,V)*C16
UC48C
0.99
1.00
0.95
T*9(C,V)*C20
FC/MC/PC43C
1.02
1.02
0.97
T*9(C,V)*C20
FC/MC/PC48C
1.03
1.07
0.98
T*9(C,V)*C20
UC48C
1.00
1.03
1.00
T*9(C,V)*D20
FC/MC/PC48D
1.03
1.06
0.94
T*9(C,V)*D20
UC48D
0.99
1.01
0.95
TM8X060A12MP11
FC/MC/PC37A
0.99
0.98
0.95
TM8X080B12MP11
FC/MC/PC43B
0.99
0.98
0.95
TM8X080C16MP11
FC/MC/PC43C
1.00
1.00
0.92
TM8X080C16MP11
FC/MC/PC48C
1.01
1.01
0.92
TM8X080C16MP11
FC/MC/PC48D
1.01
1.01
0.90
Continued on next page.