700678-LTG-E-0415
2
Johnson Controls Unitary Products
All dimensions are in inches and are subject to change without notice.
Overall height is from bottom of base pan to top of fan guard.
Overall length and width include screw heads.
Physical and Electrical Data
MODEL
TCJD30
S43S3(E)
TCJD36
S43S3(E)
TCJD42
S43S4(E)
TCJD48
S43S3(E)
TCJD60
S43S4(E)
TCJD30
S44S3(E)
TCJD36
S44S3(E)
TCJD42
S44S4(E)
TCJD48
S44S3(E)
TCJD60
S44S4(E)
Unit Supply Voltage
208-230V, 3
60Hz
460V, 3
60Hz
Normal Voltage Range
1
187 to 252
432 to 504
Minimum Circuit Ampacity
11.6
12.3
15.4
15.5
21.5
6.0
6.4
7.3
7.2
10.5
Max. Overcurrent Device Amps
2
15
20
25
25
35
15
15
15
15
15
Min. Overcurrent Device Amps
3
15
15
20
20
25
15
15
15
15
15
Compressor Type
Recip
Recip
Recip
Recip
Scroll
Recip
Recip
Recip
Recip
Scroll
Compressor Amps
Rated Load
8.1
8.6
11.1
11.2
16.0
4.2
4.5
5.2
5.1
7.8
Locked Rotor
63
68
68
88
110
30
34
34
44
52
Crankcase Heater
No
No
No
No
No
No
No
No
No
No
Factory External Discharge Muffler
No
No
No
Yes
No
No
No
No
Yes
No
Factory External Check Valve
No
No
No
No
No
No
No
No
No
No
Fan Motor Amps
Rated Load
1.4
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.8
0.8
Fan Diameter Inches
17.5
22.0
22.0
22.0
24.0
17.5
22.0
22.0
22.0
24.0
Fan Motor
Rated HP
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
Nominal RPM
1100
850
850
850
850
1100
850
850
850
850
Nominal CFM
2050
3200
3050
2950
3400
2050
3200
3050
2950
3400
Coil
Face Area Sq. Ft.
9.60
13.07
14.16
14.16
18.68
9.60
13.07
14.16
14.16
18.68
Rows Deep
1
1
1
1
1
1
1
1
1
1
Fins / Inch
23
23
23
23
23
23
23
23
23
23
Liquid Line Set OD (Field Installed)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapor Line Set OD (Field Installed)
3/4
3/4
7/8
7/8
7/8
3/4
3/4
7/8
7/8
7/8
Unit Charge (Lbs. - Oz.)
4
3 - 14
4 - 9
4 - 10
4 - 9
5 - 8
3 - 14
4 - 9
4 - 10
4 - 9
5 - 8
Charge Per Foot, Oz.
0.62
0.62
0.67
0.67
0.67
0.62
0.62
0.67
0.67
0.67
Operating Weight Lbs.
131
145
164
173
220
131
145
164
173
220
Models with “E” on the end of the model number have E-Coated coils.
1. Rated in accordance with AHRI Standard 110-2012, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, smallest matched indoor unit, and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract
the amount of refrigerant, using the difference in actual lineset length (not equivalent length) multiplied by the per foot value.
B
C
A
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A
B
C
Liquid
Vapor
30
28-1/4
24
24
3/8
3/4
36
28-1/4
29-1/2
29-1/2
42
30-1/4
29-1/2
29-1/2
7/8
48
30-1/4
29-1/2
29-1/2
60
32-1/4
34
34