background image

Pressing this button will write default values of all
temperature programs and setup menus into the unit’s
nonvolatile memory. Take care not to unintentionally
press this button when the thermostat has been
removed from the wall plate!
4.4. PROGRAMMING

You can change the preset time/and temperatures to suit
your schedule for each day of the week. Each day has
four consecutive periods. They are Morning, Day,
Evening, and Night. Separate set points are provided for
Heat and Cool.
Fan programming is similar to temperature program-
ming. It has four consecutive periods, which are inde-
pendent of the four temperature periods. The default set-
ting for your systems fan requires it to run only as
required by your environmental system. It may be pro-
grammed to maintain a minimum run time on an hourly
basis, or run continuously.

4.4.1 WEEKDAY TEMPERATURE PROGRAMMING

Rotate the dial to Set Weekday Programs. The heat

and cool set points will be displayed on the left side of
the display. The start time for the displayed day will flash
to show that this is the setting currently ready for edit.

Use the up or down arrow keys to change the start

time for this period. One period ends at the start time of
the next period. The beginning of that period may not be
any closer to the beginning of the next period than one
15 minute increment.

Press NEXT to accept the displayed start time and

advance to edit the heat set point. It will be flashing.

Use the up or down arrow keys to change Heat Set to

the temperature you desire.

Press NEXT to accept the displayed heat set point to

the temperature and advance to edit the cool set point. It
will be flashing.

There is a minimum value that must be maintained

between the heat temperature set point and Cool temper-
ature set point. The value that must be maintained is
called the Deadband. It is programmable and may be
changed in the Installer Setup menu. If you move the
heat set point temperature to close to the cool set point
temperature the cool set point temperature will move
away from the heat set point temperature to maintain the
dead band. Conversely the heat set point temperature will
move if you adjust the cool set point temperature to
close. There are programmable limits for both heat and
cool, which you will not be able to exceed. These values
are accessible from the User Setup Menu.

When you have changed the Cool set point to your

desired temperature, press NEXT to advance to the next 
period. Its start time will be flashing indicating that it is
under edit.

When all the periods for a day have been set, the start

time for the next weekday will be displayed to begin edit-

ing the settings for that day.

Rotate the dial back to RUN to and accept all current

values and end the programming session.

4.4.2 WEEKDAY FAN PROGRAMMING

Programming fan operation is similar to programming
the temperature periods and set points. Fan periods are
independent of temperature periods and are designated
P1, P2, P3, P4.

Rotate the dial to Set Weekday Programs, then press

and hold the FAN button for over 2 seconds.

The fan day and period will be displayed in the top

center and right portion of the screen. The bottom por-
tion will show the fan mode and start time for that period.
The fan mode for this period will be flashing to indicate
that it may be changed with the UP/DOWN arrow keys.
Choices are:

Auto:

default value; the fan will run only when neces-

sary for your HVAC system to maintain temperature con-
trol.

Program:

This mode will insure that during every

hour, the fan will run for the for at least the number of
minutes shown at the top left of the display, beginning at
the displayed time for this period until the beginning of
the next period. If your heating or cooling requirement
fulfills the minimum fan run time, additional fan run time
will not be requested. Activation of the fan when neces-
sary is done at twenty minute intervals for one third the
hourly run time.

■ 

On:

The On setting will run the fan continuously dur-

ing this period.

Set the desired Fan mode for his period. Press NEXT

to advance and edit this periods start time.

Use the UP or DOWN arrow keys to change the start

time. A period ends at the start time of the next period.
The beginning of a period may not be any closer to the
beginning of the next period than one 15 minute incre-
ment.

Press NEXT to advance and set the minimum fan run

time if this period is to use program mode.

Pressing NEXT again will bring you to the next period’s

mode.

When all the periods for a day have been set, the start

time for the next weekday will be displayed to begin edit-
ing the settings for that day.

The sequence of days that you may program pro-

gresses the weekdays MON - FRI, and repeats.

Then press and hold the FAN button for over 2 sec-

onds to return to Weekday temperature editing or rotate
the dial back to RUN to and accept all current values and
end the programming session.

4.4.3 WEEKEND PROGRAMMING

Weekend programming is identical to weekday program-
ming except rotate the dial to set weekend programs, and
the sequence of days that you may program is SAT, SUN
and then repeating this two day sequence.

15

4.3.3 VACATION HOLD

Use this feature to instruct the thermostat to hold a fixed
temperature for a period of from 1 to 30 days.

Verify that the unit is in Heat, Cool or AUTOCHANGE

with a temperature set point visible. The unit must be
have a temperature set point visible to enter Vacation
Hold mode.

Press and hold the HOLD button for approximately

three seconds. 

Use the UP/DOWN arrow keys to adjust the number of

days to your preference. The maximum number of
allowed days is 30.

Press NEXT. The thermostat will display the number of

days remaining in this Vacation Hold.

If the unit is in Heat mode, it will now maintain a mini-

mum temperature by controlling your heating system. If
the unit is in Cool mode, it will now maintain a maximum
temperature by controlling your cooling system.

The Vacation Hold will be complete when there are no

remaining days left and the unit will resume using the
temperature programs stored in its memory.

A Vacation Hold may also be terminated prematurely

by Pressing the HOLD button again, changing the mode
of the system, or rotating the dial.

4.3.4 DAYLIGHT SAVINGS TIME ADJUSTMENT (DST)

This button is labeled DST. When pressed it shifts the
units clock time in a three press sequence. A first press
will add 1 hour to the displayed time. A second press
subtracts one hour from the original time, and a third
press returns the unit to the original time. After one
minute with no new DST button presses, the sequence is
reset staring with the current displayed time.

4.3.5 AIR FILTER

This unit incorporates a timer, which records the number
of hours the thermostat has activated the fan. This timer
is intended to indicate when your HVAC systems filter
should be cleaned or replaced.

Refer to the User setup menu to set the number of

hours the timer will use to indicate that changing the filter
is recommended.

To view the number of hours the thermostat has acti-

vated the fan since the last timer reset, rotate the dial to
the AIR FILTER position.

To reset the timer press the UP or Down arrow key

once. Pressing an arrow key again will toggle between
0000 and the current value. The value in display when
you exit this mode will be the value retained in memory.
Leave the value at 0000 to reset the timer.

To exit the AIR FILTER mode, rotate the dial to another

position.

4.3.6 ENERGY USAGE

Your thermostat records the total number of hours the
thermostat has activated heating and cooling with six
separate timers. They measure:

Today’s cumulative heating time 

Today’s cumulative cooling time 

Yesterdays cumulative heating time 

Yesterdays cumulative cooling time 

Total cumulative heating time 

Total cumulative cooling time 

To view this set of timer values:

Rotate the dial to the ENERGY USAGE position. Timer

values will repeatedly display the above sequence.

The cumulative timers may be reset by pressing the

UP or Down arrow key once. Pressing an arrow key
again will toggle between 00:00 and the current value.
Pressing the UP or Down arrow key also stops the scroll-
ing.

Press NEXT to resume scrolling.

When you rotate the dial to another mode, the current

values will be the values retained in memory. Leave the
value at 00:00 to reset the cumulative timers.

4.3.7 FUTURE OUTDOOR SENSOR

An optional outdoor sensor may be installed to enable
the thermostat to display the temperature outside your
home. This sensor may also be used to instruct the unit
to switch from a heat pump to another source of heat.
Once installed the outdoor temperature will alternate with
the time in the display. To install an outdoor sensor refer
to the Installation Section of this manual. To enable an
outdoor sensor or change heat pump settings refer to the
Installers Setup Section of this manual.

4.3.8 FUTURE REMOTE INDOOR SENSORS

Up to three optional indoor sensors may be installed. The
temperature measurements of all active indoor sensors
will be averaged and used in temperature control. With
remote indoor sensors functioning, the units’ internal
temperature sensor may be enabled or disabled to allow
the thermostat to be mounted in locations that would
otherwise be non-ideal.
To install indoor temperature sensors refer to the
Installation Section of this manual. To enable or disable
the units internal sensor or other remote indoor tempera-
ture sensors refer to the Installers Setup Section of this
manual.

4.3.9 RESET

There are two RESET buttons on the rear of the unit’s cir-
cuit board. They are the Hardware and Software RESET
buttons.

4.3.9.1 HARDWARE RESET (H/W RESET)

The H/W RESET button restarts your thermostats pro-
gram at the beginning of normal operation. This button is
generally of little use to an owner.

4.3.9.2 SOFTWARE RESET (S/W RESET)

The S/W RESET button restarts your thermostats pro-
gram at initialization. It may be used to reset every pro-
grammable value to it’s default setting.

14

Содержание LuxPro EVERYTHING'STAT PSP722E

Страница 1: ... 4 2 USER SETUP MENU 12 4 2 1 ACCESS AND NAVIGATE USER SETUP MENU 12 4 2 2 KEYBOARD LOCK 12 4 2 3 BEEP 12 4 2 4 TEMPERATURE DISPLAY FORMAT F C DISPLAY 13 4 2 5 CLOCK FORMAT 13 4 2 6 CALIBRATION OFFSET 13 4 2 7 MAXIMUM HEAT SETTING 13 4 2 8 MINIMUM COOL SETTING 13 4 2 9 SMART RECOVERY 13 4 2 10 FILTER LIMIT 13 4 2 11 USER SETUP MENU 13 4 3 ADVANCED FEATURES AND OPERATION 13 4 3 1 EMERGENCY HEAT 13 ...

Страница 2: ...Differential Cycle Rate Programmable Length Minimum Run Time Programmable Auto Changeover Dead Band Programmable Fan Delays For Heat Cool In Both On And Off 2 COMPATIBILITY Your PSP722E is compatible with most 24 volt gas oil or electrical Heating and or Cooling systems It cannot be used with 120 volt heating systems Ask your dealer for other LUXPRO thermostats to control those systems 2 1 HEAT ST...

Страница 3: ...zing the tabs into the body Separate the unit from its base plate by pulling the body outward from the bottom NOTE If you are mounting the base to a soft material like plasterboard or if you are using the old mounting holes the screws may not hold Drill a 3 16 in 4 8mm hole at each screw location and insert the plastic anchors provided Then mount the base as described below Route the wires through...

Страница 4: ...RING OPTIONS Though not shown here additional second stages may be used where applicable Be sure to enable them properly in the Installer Setup menu W2 is second stage heat E is emergency heat and freeze protection Y2 is second stage cool or second stage heat pump OPTIONAL O or B terminals may be used to power heat ing dampers or changeover valves in any system config uration OPTIONAL C terminal m...

Страница 5: ...CAL 2 WIRE HEAT HOOKUP 24 VAC AND MILLIVOLT SYSTEMS XFMR GAS VALVE ACLINE SYSTEMTYPE FURNACE 01 HEATSTAGES 1 02 COMPRESSORSTAGES 0 03 MODES Heat Off 04 HEATFANCONTROL GAS 09 TYPICALINSTALLERSETUP OPTIONALCOMMON ALLOWSUSEOF SYSTEMPOWER 1 NOTES JUMPER PROVIDED SYSTEM COMMON G O Y2 Y1 RC C RH W1 W2 E B TYPICAL 24VAC 3 WIRE HEAT HOOKUP WHERE 3RD WIRE IS FAN WIRE FAN XFMR GAS VALVE ACLINE TYPICALINSTAL...

Страница 6: ... 1 03 MODES Ht Off Cl Auto 04 HEATFANCONTROL GAS 09 OPTIONALCOMMON ALLOWSUSEOF SYSTEMPOWER 1 NOTES G O Y2 Y1 RC C RH W1 W2 E B TYPICAL 5 WIRE HOOKUP SINGLE STAGE HEATING AND COOLING COOLING XFMR1 FAN GAS VALVE HEATING XFMR2 ACLINE ACLINE COOL COMMON COMPRESSOR TYPICALINSTALLERSETUP SYSTEMTYPE FURNACE 01 HEATSTAGES 1 02 COMPRESSORSTAGES 1 03 MODES Ht Off Cl Auto 04 HEATFANCONTROL GAS 09 OPTIONALCOM...

Страница 7: ...ROVIDED SYSTEMCOMMON TYPICALINSTALLERSETUP SYSTEMTYPE HEATPUMP 01 HEATSTAGES 1 02 COMPRESSORSTAGES 1 03 MODES Ht Off Cl EmHt Auto 04 HEATFANCONTROL ELECTRIC 09 G O Y2 Y1 RC C RH W1 W2 E B USE 2 SEPARATE SINGLE STAGE HEATERS AS A 2 STAGE HEAT SYSTEM SYSTEM XFMR1 HEATER 1 HEATER 2 SYSTEM XFMR2 ACLINE ACLINE SYSTEM1 COMMON SYSTEM2 COMMON OPTIONALCOMMON ALLOWSUSEOF SYSTEMPOWER 1 NOTES TYPICALINSTALLER...

Страница 8: ...ERSETUP SYSTEMTYPE FURNACE 01 HEATSTAGES MATCHSYSTEM 02 COMPRESSORSTAGES MATCHSYSTEM 03 MODES Ht Off Cl Auto 04 HEATFANCONTROL ELECTRIC 09 G O Y2 Y1 RC C RH W1 W2 E B TYPICAL MULTI STAGE STAGE HEAT PUMP WITH OPTIONAL AUX AND EMERGENCY HEAT 2 OR 3 STAGES HEAT 2 STAGES COOL FAN SYSTEM XFMR AUX EM HEAT REVERSING VALVE HEAT PUMP STAGE2 COMPRESSOR STAGE1 COMPRESSOR ACLINE JUMPER PROVIDED SYSTEMCOMMON O...

Страница 9: ... cooling In this mode an additional stage of Aux Heat may also be activated through the W1 terminal 3 7 1 2 HEAT STAGES Set this to the number of non compressor driven heat stages to use for temperature control by this system 3 7 1 3 COMPRESSOR STAGES COOL HEAT PUMP STAGES Set the number of compressor driven system stages to use for temperature control These stages include all cooling or heat pump...

Страница 10: ...perature will be displayed alter nately with time The word OUT will be visible to the right of the temperature while the outside temperature is dis played 3 7 1 17 INTERNAL TEMPERATURE SENSOR This setting enables and disables the thermostats internal temperature sensor It may only be disabled if there are indoor remote sensors present and enabled 3 7 1 18 FUTURE INDOOR REMOTE SENSOR 1 2 3 Used to ...

Страница 11: ...s supplied from the factory the following ENERGY STAR approved program will be used for temperature control This program and all other settings maybe restored to their default values via a SOFTWARE RESET Default Daily Temperature Program Period HeatMode CoolMode Morning 6 00AM70 F 6 00AM78 F Day 8 00AM62 F 8 00AM85 F Evening 6 00PM70 F 6 00PM78 F Night 10 00PM62 F 10 00PM82 F 4 1 4 MODES Because o...

Страница 12: ...e momentarily press Setup Button Selections can be changed by pressing the UP DOWN button Moving from one menu item to the next and accept ance of changes is done by pressing the NEXT button All changes become effective when the unit exits the User Setup mode The User Setup mode will be exited when the Setup button is pressed again or if no other keys are pressed for 20 seconds 4 2 2 KEYBOARD LOCK...

Страница 13: ...ta necessary to predict a Smart recovery time 4 2 10 FILTER LIMIT Your thermostat will warn you that your HVAC systems air filter should be changed after the systems fan has run the number of hours that this setting has been pro grammed for A general rule of thumb is to assume that the fan will run at 1 3 duty cycle A 90 day filter will then be good for 90 24 3 720 hours This is the default value ...

Страница 14: ...mer To exit the AIR FILTER mode rotate the dial to another position 4 3 6 ENERGY USAGE Your thermostat records the total number of hours the thermostat has activated heating and cooling with six separate timers They measure Today s cumulative heating time Today s cumulative cooling time Yesterdays cumulative heating time Yesterdays cumulative cooling time Total cumulative heating time Total cumula...

Страница 15: ...cating that it is under edit When all the periods for a day have been set the start time for the next weekday will be displayed to begin edit ing the settings for that day Rotate the dial back to RUN to and accept all current values and end the programming session 4 4 2 WEEKDAY FAN PROGRAMMING Programming fan operation is similar to programming the temperature periods and set points Fan periods ar...

Страница 16: ...bove the temperature set point Stage one of a cooling system will be deactivated at the value of swing 1 below the temperature set point Stage two of a heating system will be activated at the value of swing 1 swing 2 below the temperature set point The auxiliary heat indicator AUX HT will be visible when a second stage of heat is activated Stage two of cooling will be activated at the value of swi...

Отзывы: