background image

3.6. INSTALL BATTERIES

Install batteries at this time. For instructions, see BAT-
TERY INSTALLATION.

3.7. INSTALLER SETUP

Configuration items are selected from the Installer Set up
Menu. They are stored in non-volatile RAM, and will be
preserved even in the event that the unit’s batteries are
run down, or removed, or the hardware reset on the rear
of the unit’s circuit board of the thermostat is pressed.

NOTE: Pressing the S/W RESET button on the rear of the
unit’s circuit board will write default values of all temperature
programs and setup menus into the unit nonvolatile memory.
Take care not to inadvertently press this button when the ther-
mostat has been removed from the wall plate!

3.7.1 ACCESS AND NAVIGATE INSTALLER SETUP

MENU
Note: Insure that all relays are off before making changes in
the installer menu. There are two methods, which may be
used to do this. Place the unit in the OFF mode and wait for 5
minutes or Press the H/W RESET button on the rear of the
unit’s circuit board. Take care not to inadvertently press the
S/W RESET button.

To enter the Installer Setup Menu press and hold the

Setup Button for 10 seconds.

Use the NEXT button to scroll through its options. As

you proceed the menu item number will be displayed in
the left portion of the screen.

Selections can be changed by pressing the UP/DOWN

button.

Moving from one menu item to the next and accept-

ance of changes is done by pressing the NEXT button.

All changes become effective when the unit exits the

Installer Setup mode.

The Installer Setup mode will be exited when the Setup

button is pressed again, or, if no other keys are pressed
for 20 seconds. 
All settings, their choices and default values are given in
INSTALLER SETUP MENU WITH FURNACE SYSTEM
TYPE SELECTED: and INSTALLER SETUP MENU WITH
HEAT PUMP SYSTEM TYPE SELECTED AND FUTURE
OUTDOOR SENSOR ENABLED.

3.7.1.1 SYSTEM TYPE

This option determines whether the thermostat is to con-
trol a furnace and air conditioning system or heat pump
system.

In furnace mode the unit will make the proper W ter-

minals live for Heating, and the proper Y terminals live
for cooling.

In Heat Pump mode the unit makes the proper Y ter-

minals live for the first and second stages of a heat pump
unit during heating or cooling. In this mode an additional
stage of Aux Heat may also be activated through the W1
terminal.

3.7.1.2 HEAT STAGES

Set this to the number of non-compressor driven heat
stages to use for temperature control by this system.

3.7.1.3 COMPRESSOR STAGES (COOL/HEAT PUMP
STAGES)

Set the number of compressor driven system stages to
use for temperature control. These stages include all
cooling or heat pump stages to be used for temperature
control by this system.

3.7.1.4 MODES

The modes setting selects what system modes will be
available to the user. The selections available are system
mode dependant:

Heat-Off

Cool-Off

Heat-Off-Cool

Heat-Off-Cool-Auto (Furnace Mode) or

Heat-Off-Cool-Em Heat-Auto (Heat Pump Mode)

3.7.1.5 MINIMUM RUN TIME

Minimum Run Time provides compressor protection and
prevents short cycling. Compressor stages are held off
for a minimum of this time. During program run this is
also the minimum on time.

3.7.1.6 HEAT PUMP LOCKOUT

This menu item is available only in Heat Pump Mode with
an operational outdoor temperature sensor. Enabling this
option allows the thermostat to disable a heat pump and
request AUX Heat below the Heat Pump Lockout
Temperature.

3.7.1.7 HEAT PUMP LOCKOUT TEMPERATURE

This menu item is available only in Heat Pump Mode with
an operational outdoor temperature sensor. With it you
may set the outdoor temperature at which the thermostat
will cease to call for heat pump sourced heat, and use the
alternate AUX Heat source.

3.7.1.8 DEADBAND

When using auto-changeover, deadband provides a disal-
lowed temperature range between the maximum heat
temperature set point and minimum cool temperature set
point. Deadband may be set from 3 to 5 degrees. With
auto-changeover active and the Deadband set to 3°F and
heat set to 70°F the minimum allowed cool temperature
set point will be 73°F. If the cool temperature set point is
lowered, then the heat temperature set point will be low-
ered by the same amount maintaining the 3°F Deadband.

3.7.1.9 SWING 1

Swing 1 sets the temperature variation the system allows
above the temperature set point before switching the first
stage heat source off, or below the temperature set point
before switching the first stage heat source on. In Cool,
Swing 1 sets the temperature variation the system allows
above the temperature set point before switching first
stage of cooling on, or below the temperature set point
before switching the first stage of cooling off. 

9

8

G O Y2 Y1 RC C RH W1 W2 E B

MULTI-STAGE FURNACE HEAT

AND COOLING HOOKUP

FAN

COOLING

XFMR

HEATING

XFMR

HEATER

AIR CONDITIONER

STAGE 2

COMPRESSOR

STAGE 1

COMPRESSOR

AC LINE

AC LINE

OPTIONAL COMMON
ALLOWS USE OF
SYSTEM POWER
EITHER SECOND
STAGE MAY BE 
OMITTED

[1]

[2]

NOTES:

STAGE

1

STAGE

2

COOL

COMMON

HEAT

COMMON

TYPICAL INSTALLER SETUP:

SYSTEM TYPE = FURNACE

[01]

HEAT STAGES
=(MATCH SYSTEM)

[02]

COMPRESSOR STAGES
= (MATCH SYSTEM)

[03]

MODES = H

t

-Off-Cl-Au

t

o

[04]

HEAT FAN CONTROL
= ELECTRIC

[09]

G O Y2 Y1 RC C RH W1 W2 E B

TYPICAL MULTI-STAGE STAGE HEAT PUMP WITH

OPTIONAL AUX AND EMERGENCY HEAT

(2 OR 3 STAGES HEAT, 2 STAGES COOL)

FAN

SYSTEM

XFMR

AUX/EM

HEAT

REVERSING

VALVE

HEAT    PUMP

STAGE 2

COMPRESSOR

STAGE 1

COMPRESSOR

AC LINE

JUMPER

PROVIDED

SYSTEM COMMON

OPTIONAL COMMON
ALLOWS USE OF
SYSTEM POWER
USE "B" OR "O" BUT
NOT BOTH

AUX HEAT AND
EMERGENCY HEAT
ARE OPTIONAL

[1]

[2]

[3]

NOTES:

TYPICAL INSTALLER SETUP:

SYSTEM TYPE = HEAT PUMP

[01]

HEAT STAGES
= MATCH SYSTEM

[02]

COMPRESSOR 
STAGES = MATCH SYSTEM

[03]

MODES = H

t

-Off-Cl-

 EmH

t

-Au

t

o

[04]

HEAT FAN CONTROL
= ELECTRIC

[09]

Содержание LuxPro EVERYTHING'STAT PSP722E

Страница 1: ... 4 2 USER SETUP MENU 12 4 2 1 ACCESS AND NAVIGATE USER SETUP MENU 12 4 2 2 KEYBOARD LOCK 12 4 2 3 BEEP 12 4 2 4 TEMPERATURE DISPLAY FORMAT F C DISPLAY 13 4 2 5 CLOCK FORMAT 13 4 2 6 CALIBRATION OFFSET 13 4 2 7 MAXIMUM HEAT SETTING 13 4 2 8 MINIMUM COOL SETTING 13 4 2 9 SMART RECOVERY 13 4 2 10 FILTER LIMIT 13 4 2 11 USER SETUP MENU 13 4 3 ADVANCED FEATURES AND OPERATION 13 4 3 1 EMERGENCY HEAT 13 ...

Страница 2: ...Differential Cycle Rate Programmable Length Minimum Run Time Programmable Auto Changeover Dead Band Programmable Fan Delays For Heat Cool In Both On And Off 2 COMPATIBILITY Your PSP722E is compatible with most 24 volt gas oil or electrical Heating and or Cooling systems It cannot be used with 120 volt heating systems Ask your dealer for other LUXPRO thermostats to control those systems 2 1 HEAT ST...

Страница 3: ...zing the tabs into the body Separate the unit from its base plate by pulling the body outward from the bottom NOTE If you are mounting the base to a soft material like plasterboard or if you are using the old mounting holes the screws may not hold Drill a 3 16 in 4 8mm hole at each screw location and insert the plastic anchors provided Then mount the base as described below Route the wires through...

Страница 4: ...RING OPTIONS Though not shown here additional second stages may be used where applicable Be sure to enable them properly in the Installer Setup menu W2 is second stage heat E is emergency heat and freeze protection Y2 is second stage cool or second stage heat pump OPTIONAL O or B terminals may be used to power heat ing dampers or changeover valves in any system config uration OPTIONAL C terminal m...

Страница 5: ...CAL 2 WIRE HEAT HOOKUP 24 VAC AND MILLIVOLT SYSTEMS XFMR GAS VALVE ACLINE SYSTEMTYPE FURNACE 01 HEATSTAGES 1 02 COMPRESSORSTAGES 0 03 MODES Heat Off 04 HEATFANCONTROL GAS 09 TYPICALINSTALLERSETUP OPTIONALCOMMON ALLOWSUSEOF SYSTEMPOWER 1 NOTES JUMPER PROVIDED SYSTEM COMMON G O Y2 Y1 RC C RH W1 W2 E B TYPICAL 24VAC 3 WIRE HEAT HOOKUP WHERE 3RD WIRE IS FAN WIRE FAN XFMR GAS VALVE ACLINE TYPICALINSTAL...

Страница 6: ... 1 03 MODES Ht Off Cl Auto 04 HEATFANCONTROL GAS 09 OPTIONALCOMMON ALLOWSUSEOF SYSTEMPOWER 1 NOTES G O Y2 Y1 RC C RH W1 W2 E B TYPICAL 5 WIRE HOOKUP SINGLE STAGE HEATING AND COOLING COOLING XFMR1 FAN GAS VALVE HEATING XFMR2 ACLINE ACLINE COOL COMMON COMPRESSOR TYPICALINSTALLERSETUP SYSTEMTYPE FURNACE 01 HEATSTAGES 1 02 COMPRESSORSTAGES 1 03 MODES Ht Off Cl Auto 04 HEATFANCONTROL GAS 09 OPTIONALCOM...

Страница 7: ...ROVIDED SYSTEMCOMMON TYPICALINSTALLERSETUP SYSTEMTYPE HEATPUMP 01 HEATSTAGES 1 02 COMPRESSORSTAGES 1 03 MODES Ht Off Cl EmHt Auto 04 HEATFANCONTROL ELECTRIC 09 G O Y2 Y1 RC C RH W1 W2 E B USE 2 SEPARATE SINGLE STAGE HEATERS AS A 2 STAGE HEAT SYSTEM SYSTEM XFMR1 HEATER 1 HEATER 2 SYSTEM XFMR2 ACLINE ACLINE SYSTEM1 COMMON SYSTEM2 COMMON OPTIONALCOMMON ALLOWSUSEOF SYSTEMPOWER 1 NOTES TYPICALINSTALLER...

Страница 8: ...ERSETUP SYSTEMTYPE FURNACE 01 HEATSTAGES MATCHSYSTEM 02 COMPRESSORSTAGES MATCHSYSTEM 03 MODES Ht Off Cl Auto 04 HEATFANCONTROL ELECTRIC 09 G O Y2 Y1 RC C RH W1 W2 E B TYPICAL MULTI STAGE STAGE HEAT PUMP WITH OPTIONAL AUX AND EMERGENCY HEAT 2 OR 3 STAGES HEAT 2 STAGES COOL FAN SYSTEM XFMR AUX EM HEAT REVERSING VALVE HEAT PUMP STAGE2 COMPRESSOR STAGE1 COMPRESSOR ACLINE JUMPER PROVIDED SYSTEMCOMMON O...

Страница 9: ... cooling In this mode an additional stage of Aux Heat may also be activated through the W1 terminal 3 7 1 2 HEAT STAGES Set this to the number of non compressor driven heat stages to use for temperature control by this system 3 7 1 3 COMPRESSOR STAGES COOL HEAT PUMP STAGES Set the number of compressor driven system stages to use for temperature control These stages include all cooling or heat pump...

Страница 10: ...perature will be displayed alter nately with time The word OUT will be visible to the right of the temperature while the outside temperature is dis played 3 7 1 17 INTERNAL TEMPERATURE SENSOR This setting enables and disables the thermostats internal temperature sensor It may only be disabled if there are indoor remote sensors present and enabled 3 7 1 18 FUTURE INDOOR REMOTE SENSOR 1 2 3 Used to ...

Страница 11: ...s supplied from the factory the following ENERGY STAR approved program will be used for temperature control This program and all other settings maybe restored to their default values via a SOFTWARE RESET Default Daily Temperature Program Period HeatMode CoolMode Morning 6 00AM70 F 6 00AM78 F Day 8 00AM62 F 8 00AM85 F Evening 6 00PM70 F 6 00PM78 F Night 10 00PM62 F 10 00PM82 F 4 1 4 MODES Because o...

Страница 12: ...e momentarily press Setup Button Selections can be changed by pressing the UP DOWN button Moving from one menu item to the next and accept ance of changes is done by pressing the NEXT button All changes become effective when the unit exits the User Setup mode The User Setup mode will be exited when the Setup button is pressed again or if no other keys are pressed for 20 seconds 4 2 2 KEYBOARD LOCK...

Страница 13: ...ta necessary to predict a Smart recovery time 4 2 10 FILTER LIMIT Your thermostat will warn you that your HVAC systems air filter should be changed after the systems fan has run the number of hours that this setting has been pro grammed for A general rule of thumb is to assume that the fan will run at 1 3 duty cycle A 90 day filter will then be good for 90 24 3 720 hours This is the default value ...

Страница 14: ...mer To exit the AIR FILTER mode rotate the dial to another position 4 3 6 ENERGY USAGE Your thermostat records the total number of hours the thermostat has activated heating and cooling with six separate timers They measure Today s cumulative heating time Today s cumulative cooling time Yesterdays cumulative heating time Yesterdays cumulative cooling time Total cumulative heating time Total cumula...

Страница 15: ...cating that it is under edit When all the periods for a day have been set the start time for the next weekday will be displayed to begin edit ing the settings for that day Rotate the dial back to RUN to and accept all current values and end the programming session 4 4 2 WEEKDAY FAN PROGRAMMING Programming fan operation is similar to programming the temperature periods and set points Fan periods ar...

Страница 16: ...bove the temperature set point Stage one of a cooling system will be deactivated at the value of swing 1 below the temperature set point Stage two of a heating system will be activated at the value of swing 1 swing 2 below the temperature set point The auxiliary heat indicator AUX HT will be visible when a second stage of heat is activated Stage two of cooling will be activated at the value of swi...

Отзывы: