S P E C I F I C AT I O N   S U B M I T TA L

Page

Job Name:

Job Number:

Model Numbers:

Vive

HMS-0, HMS-1, HMS-2

Wireless Hub

3691044-04g   7   03.23.21

Range Diagrams

22 m 

Maximum

22 m 

Maximum

30 m 

30 m

Range with multiple Vive hubs

  All wireless devices to be associated to the Vive hub must be within 22 m of the Vive hub and must be on the same 

floor as the Vive hub. 

 Note: 

Vive hubs should be mounted greater than 3 m apart on the same floor.

 Note: 

Lutron requires that the Vive hub not be installed above metal ceilings or tiles with a metal backing.

 Note:

 A corporate Wi-Fi network can interfere with the Wi-Fi on the Vive hub. Where a corporate Wi-Fi network exists, 

it is recommended to do the following: 

•  Connect the Vive hub to the corporate network using the Ethernet connection on the hub and disable Wi-Fi on 

the hub.

 Note:

 Vive hubs should be mounted greater than 3 m from a Wi-Fi router or access point.

30 m 

30 m

 

Private Office

PowPak Dimming 
Module

Conference Room

PowPak Dimming Module

Open Office

PowPak Relay Module

Personal Control

Pico Remote Control

Sensors

Radio Powr Savr 
Occupancy Sensor

Setup, Monitor  
and Control

Vive Hub

9 m 

Maximum 

1

9 m 

Maximum 

1

9 m 

Maximum 

1

9 m 

Maximum 

1

22 m 

Maximum

Vive Hub RF 

coverage

1

  

NOTE: 

Wireless sensors and controls must be located within 

9 m of the associated control module.

•  Metal ceiling grids must have a > 3 mm gap of non-metal 

material which extends the entire length of the tile on at least 

one edge. This is often achieved by foam spacers that are 

used to prevent tile-to-tile rattling.

•  Metal ceiling grids which are continuous (with no gap) or those 

that are interlocked, must have a total surface area that is 

less than 81 m

2

 for each section. The overall space can be 

larger as long as there are non-metal sections bordering or 

intersecting the metal sections.

7

Содержание Vive HMS-0

Страница 1: ...multi color LED provides feedback on what mode the hub is in Connects directly to any smartphone tablet or computer using built in Wi Fi 2 4 GHz 802 11b g using WPA2 Security Ethernet 10 100 Mbps con...

Страница 2: ...holidays Allows scheduling events on specific day of the year Provides calculated energy data for PowPak modules Create and edit areas Tune area light levels by trimming the high end and low end outp...

Страница 3: ...pp Maximum of 50 scenes are supported Requires Vive hub software 01 13 or higher Programmable CCI The second contact closure input CCI 2 can be programmed to activate a scene Scene activation o Set a...

Страница 4: ...re Input Terminals First contact closure input CCI 1 is to be used for initiating load shed only The second contact closure input CCI 2 may be programmed to activate a scene If activating a scene a de...

Страница 5: ...Hub Model Numbers includes power supply and mounting adapter HMS 0 FM Starter Vive hub flush mount adapter and power supply HMS 1 FM Vive hub flush mount adapter and power supply HMS 2 FM Premium Viv...

Страница 6: ...re shown as mm Surface mount Adapter Details Knockouts for conduit Vive Hub Top View Side View 173 135 71 38 Flush mount Adapter Top View Side View 165 79 Surface mount Adapter Top View Side View 122...

Страница 7: ...b Note Vive hubs should be mounted greater than 3 m from a Wi Fi router or access point 30 m 30 m Private Office PowPak Dimming Module Conference Room PowPak Dimming Module Open Office PowPak Relay Mo...

Страница 8: ...tyle junction box Supplied US style junction box Vive hub Flush mount adapter Vive Hub CCI1 COM 24 V COM CCI2 Red Blue Ethernet 10 100 LAN 24 V 220 240 V Ceiling Power supply Vive hub Surface mount ad...

Страница 9: ...rest technologies The Vive hub can be deployed in one of two ways Dedicated Lutron Network Connected to the corporate IT network via Ethernet The Vive hub must be connected via Ethernet to access cer...

Страница 10: ...ed to discover the Vive hub when mDNS is not available 5353 UDP Ethernet Used to discover the Vive hub via mDNS Configurable TCP Ethernet Used for OpenADRR Specified by utility company Inbound 443 TCP...

Страница 11: ...ommunication link Inter Hub Link Wiring Security 1 continued Link segment 100 m Ports Used Traffic Port Type Connection Description Outbound 47808 configurable UDP Ethernet Used for BACnet integration...

Страница 12: ...LB P LRF4 OHLB P LRF4 OWLB P In Line Phase Control Dimmers2 RMMS 250 NE The Lutron logo Lutron Lutron Clear Connect Pico PowPak Radio Powr Savr Vive Vue and Vive are trademarks or registered trademark...

Отзывы: