Step 5
Feed and Load Wiring
You do not need to install a temporary distribution
panel. Connect load wires into the appropriate
terminal blocks. Each input breaker can supply
power to a load while the bypass jumper protects
the switch module from load faults.
L
SL
Input circuit breaker
Bypass jumper protects the
switch module from load
faults.
Warning!
Verify that the Softswitch128
panel is fed from the correct voltage. A
feed miswire or loss of a feed neutral can
cause over-voltage damage to the
equipment.
Feed and Load Wiring
3Ø 4W
Isolation Switch
Accepts:
#14 AWG (2.0 mm
2
)
to #2 AWG (35 mm
2
)
Panels with Branch Circuit Breakers
230V (CE), 220-240V (non-CE)
XPS
Model
Switch
Legs
Feed
Type
Max
Feed
XPS8
XPS12
XPS16
XPS20
XPS24
8
12
16
20
24
125 A
Use the charts below to determine feed and load wiring sizes for Softswitch128 panels. Note that load circuit
wiring sizes are shown bottom right.
Load Circuit Wiring
Terminal blocks accept one #14 AWG (1.5 mm
2
)
through #10 AWG (4.0 mm
2
) or two #18 AWG
(1.0 mm
2
) through #16 AWG wire. Preferred entry
is from the top of the panel.
Feed
Through
Feed-Through Panels
230V (CE), 220-240V (non-CE)
XPS
Model
Switch
Legs
Feed
Type
Max
Feed
XPS8
XPS12
XPS16
XPS20
XPS24
XPS28
XPS32
XPS36
XPS40
XPS44
XPS48
8
12
16
20
24
28
32
36
40
44
48
16 A
Temporary Lighting