PowPak
®
Fixture Sensor
Regulatory Approvals
• FC-SENSOR, FC-VSENSOR:
– cULus Listed
Power/Load
• Operating voltage: 12 V
-
• Operating current: 25 mA
• IEC SELV / NEC
R
Class 2
Environmental
• Ambient operating temperature: 32 °F to 104 °F
(0 °C to 40 °C), 0%–90% humidity, non-condensing;
indoor use only
Warranty
• 5 Year Limited Warranty. For additional Warranty
information, please visit: www.lutron.com/
TechnicalDocumentLibrary/Sensor_Warranty.pdf
Wiring
• Sensor wires are IEC SELV / NEC
R
Class 2 rated
Settings
• Occupancy sensor timeout (fixture sensor): 15 minutes
• Utilizes a green laser pointer (by others, not a Lutron
R
product) to associate Pico
R
wireless controls and
Radio Powr Savr
™
sensors to PowPak
®
wireless
fixture controls via RF. See Lutron
R
application note
#407 (www.lutron.com/GreenLaserAppNote) for more
information.
– Green laser specifications:
∙
Wave output: constant
∙
Wavelength: 532 nm
∙
Output power: 5 mW maximum
• 2-wire connection between a PowPak
®
fixture sensor
and a PowPak
®
wireless fixture control
– The wires are interchangeable to eliminate miswiring
– The sensor comes with 2 ft (0.6 m) of wires
– If hanging pendant fixtures, the maximum wire
length between fixture sensor and fixture control is
12 ft (3.7 m). Sensor should be mounted no more
than 2 ft (0.6 m) from the fixture.
Features
Occupancy Sensor:
• Passive infrared motion detection with exclusive Lutron
R
XCT
T
Technology for major and minor motion detection.
• 360˚ field-of-view.
• Up to 300 ft
2
(27.9 m
2
) major motion coverage and
150 ft
2
(13.9 m
2
) minor motion coverage.
Daylight Sensor:
• Daylight sensor has simple, automatic calibration
out-of-the-box.
• Designed to give a linear response to changes in
perceived light level.
• Detects ambient light level changes from 0 to 1600 lx
(0 to 150 fc).
• Daylight compensation through Lutron
R
reliable closed
loop proportional control. For more information,
see www.lutron.com/TechnicalDocumentLibrary/
daylighting_white-paper.pdf
Sensor
Green Laser
!
WARNING
DANGER
Eye injury and/or blindness hazard;
avoid direct eye exposure to laser beam.
• Use of laser pointer is NOT recommended for use with Lutron
R
products located near reflective surfaces.
• Do NOT aim or shine laser pointers at any person, pet, vehicle, or aircraft directly, or through reflection by mirrors or
other shiny surfaces. Do NOT view the laser beam through binoculars, magnifying glass, or other optical devices.
• Do NOT allow children to use laser pointers.
•
Read and follow the laser pointer manufacturer’s instructions on safe use.
In the event of injury, get
medical attention immediately.
4