Appendix A: More about Class 2/PELV Wiring

This appendix explains the Class 2/PELV wiring used to carry communications between PRO AV DLC Control
Units and Wallstation Controls.

Lutron requires that you connect (daisy-chain) all PRO AV DLC Control Units, Wallstations, and Accessories with
two twisted pair for operation. If shielded wire is used, the drain wires must be connected to each other or to Ter-
minal D, if present. Drain wires should not be connected to Earth/Ground.

One pair is for the low-voltage power wiring that enables each PRO AV DLC Control Unit to supply power to up
to two Wallstations. Connect this twisted pair to terminals 1 (COMMON) and 2 (12VDC). Terminate the 12VDC
power to ensure that each Control Unit powers 

no more than two Wallstation Controls.

The second pair is for a data link (up to 2000 ft. or 450 m long) that enables Wallstation Controls to
communicate with PRO AV DLC Control Units. Connect this twisted pair to terminals 3 (MUX) and 4 (MUX) of
every Control Unit and Wallstation.

Each twisted pair in the Class 2 wiring link should consist of two #18 AWG (1.0 mm

2

) stranded conductors.

Lutron offers a one-cable (non-plenum), low-voltage solution. Please ask for P/N GRX-CBL-
346S.

Recommended unshielded cables: 

For non-plenum installations, use (2) Belden 9470, (1) Belden 9156, or (2) Liberty 181P/2C-EX-GRN, or
equivalent.

For plenum installations, use (2) Belden 82740, or equivalent.

Wallstation circuits are classified as Class 2 circuits (U.S.A) (IEC). Unless otherwise specified, the voltages do not exceed 24VAC or 15VDC. As Class 2
circuits, they comply with the requirements of NFPA 70, National Electrical Code (NEC). When installing and wiring to these Wallstations, follow all applicable
national and/or local wiring regulations. External circuits connected to input, output, RS232, DMX512, and other communication terminals of Wallstations,
must be supplied from a Listed Class 2 source.

The PRO AV DLC Control Unit Class 2 circuit is 12VDC.

EACH TERMINAL CAN ACCEPT UP TO 2 #18
AWG (1.0 mm

2

) WIRES

CLASS 2/PELV
POWER WIRING:
2: 12VDC
1: COMMON

2 TWISTED PAIRS
#18 AWG (1.0 mm

2

)

DATA LINK:
4: MUX
3: MUX

Page 10

Appendix B: Installing an External Power Supply

Use an external power supply if you need to power more than two Wallstations or Accessories from a single Control Unit or if your wire lengths exceed
maximums. Power supplies do not boost data line signals. The distance limitation for the data line is 2000 ft. (450 m).
Install an external Class 2/PELV rated 12VDC power supply as shown below. This power must be Class 2/PELV rated and be a regulated supply rated for at
least 50 mA per Wallstation on the link. It can supply power to up to 15 Wallstations, enabling you to use up to 15 Wallstations with one Control Unit.
Make sure you review the manufacturer’s instructions before installing.

Lutron 12VDC transformer for 120V applications (P/N GRX-12VDC).

PRO AV DLC CLASS 2/PELV TERMINALS

1 TWISTED PAIR 

#18 AWG (1.0 mm

2

)

OR LARGER

2 TWISTED PAIR 

#18 AWG (1.0 mm

2

)

OR LARGER

WALLSTATION

15 WALLSTATIONS OR ACCESSORIES (MAXIMUM)

COMMON

(+) 12VDC

1 #18 AWG (1.0 mm

2

)

TO POWER SOURCE

GRX-12VDC

IMPORTANT WIRING NOTES!

1.

Connect the +12VDC wire from the power supply to the terminal 2 connection on all Wallstations. Do not connect this wire to any PRO AV Control Units on
the link. Be sure that the terminal 1 connection is made to all Wallstations and Control Units.

2.

Lutron recommends these maximum distances from the external 12VDC power supply to the last Wallstation:

#18 AWG (1.0 mm

2

) wire: 300 ft. (90 m).

#12 AWG (2.5 mm

2

) wire: 1000 ft. (300 m).

Note that the allowable maximum distance depends on the number of Wallstations in the system. Please see Application Note W14 or consult the Lutron
Technical Assistance Hotline for more detailed information.

WALLSTATION

Содержание PAV6M-120

Страница 1: ...ltage lighting do not remove factory installed bypass jumpers on load circuit terminals until load circuits are tested see start up procedure on page 6 The Pro AV DLC dimming modules are designed to o...

Страница 2: ...or CE models No zone may be loaded with more than 800 W Maximum load capacity for Control Unit is 2 000 W 2300 W for CE Unit must not carry more than 16A of total lighting load 10A for CE models Descr...

Страница 3: ...s 2 Plan placement of modules Modules must be mounted vertically Make sure that nothing blocks the air channel between the back of the module and the wall Leave 6 152 mm of space above and below modul...

Страница 4: ...es must have a load of at least 25W 40 W for CE models No zone may be loaded with more than 800 W Maximum load capacity for Control Unit is 2 000 W 2300 W for CE Unit must not carry more than 16A of t...

Страница 5: ...NTGRX 4B Scene Selection Control NTGRX 4M Master Control NTGRX 4PS Partition Control GRX CIR Infrared Ceiling Receiver GRX 4S DW ArchitraveTM Door Jamb Control GRX AV Interface Control EGRX 4S Europea...

Страница 6: ...ermine the function of the unit s two buttons Scene 1 and Off Scene 9 Scene 10 Scene 13 Scene 14 Panic Control Fine Tuning Control Partition Status Zone Lockout Sequencing Scenes 5 16 Scenes 1 to 4 Sc...

Страница 7: ...hting effects and make sure the Control Unit is working correctly To set up the PRO AV DLC Control Unit enter the setup mode and use the menu of setup codes that appear in the DISPLAY window Step by s...

Страница 8: ...eased A capital letter indicates a button was pushed and a lowercase letter indicates a button was released The following is a list of how addresses are indicated Set up a Wallstation Control to talk...

Страница 9: ...ed The response will be a ss followed by a string of eight ASCII characters one for each PAV control unit Each character represents the scene of each PAV control unit indicated by an A scene 11 will b...

Страница 10: ...nput output RS232 DMX512 and other communication terminals of Wallstations must be supplied from a Listed Class 2 source The PRO AV DLC Control Unit Class 2 circuit is 12VDC EACH TERMINAL CAN ACCEPT U...

Страница 11: ...n 68 75 mm deep minimum When mounting several units in a vertical layout one underneath the other allow at least 4 1 2 in 11 cm between units 3 Strip 1 2 in 12 mm insulation from 12 2 5 mm2 75 C coppe...

Страница 12: ...ng relay that can handle the in rush current of ballasts The inter face gives PRO AV DLC Series Control Units the ability to both dim and switch electronic ballasts such as Lutron s Eco 10 TVE models...

Страница 13: ...one from 800W VA to 1920W VA with the HP 2 3840W VA with the HP 4 5760W VA with the HP 6 Up to 28 800W VA by daisy chaining five HP 6 Modules HP 2 4 6 Modules can also accept 277V input load power fee...

Страница 14: ...urrent Check each zone output current add power boosters where necessary GRX 8IT GRX IT SCENE BUTTONS 1 4 OFF BUTTON MASTER RAISE LOWER Appendix F Infrared Transmitters Receivers Transmitters Receiver...

Страница 15: ...Page 15...

Страница 16: ...0657 All others 1 610 282 3800 Website address www lutron com E mail product lutron com Warranty Lutron warrants each new unit to be free from defects in materials and workmanship and to perform under...

Отзывы: