Appendix D: GRX-TVI 0-10 Volt Ballast/Switching Interface
Specifications
FEATURES
■
Provides a Class 2/PELV isolated 0-10V output signal.
Complies with UL Standard 508.
■
Accepts a zone output signal from PRO AV DLC
(100-127V, 220-240V, 50/60Hz).
CONTROL INPUT POWER RATING
100-127/220-240V, 50/60Hz
0-10V OUTPUT RATING
10µA-300mA (maximum 150 ballasts)
OUTPUT SWITCHING
100-277V
230V
CAPACITIES
Fluorescent (with Lutron TVE ballasts) ...........................16A.............10A
Fluorescent (with ballasts by others) ...............................5A..............5AX
Incandescent...................................................................16A.............10A
Low Voltage....................................................................16A.............10A
Metal Halide ...................................................................16A.............10A
Neon/Cold Cathode ........................................................16A.............10A
Motor @ 100-127V ......................................................1/4Hp ............—
Motor @ 220-277V ......................................................1/2Hp ............—
TERMINALS
Two #12-20AWG conductors per terminal.
MOUNTING
NEMA Type 1 enclosure, indoor use only.
ENVIRONMENTAL
32—104 ˚F (0—40 ˚C).
WEIGHT
4.25 lb. (2kg)
The GRX-TVI provides 0-10V control and
ballast switching capabilities in one en-
closure. The interface gives PRO AV DLC
Control Units the ability to control 0-10V
ballasts powered by 120V to 277V and
provides a switching relay that can handle
the in-rush current of ballasts. The inter-
face gives PRO AV DLC Series Control
Units the ability to both dim and switch
electronic ballasts, such as Lutron’s Eco-
10 (TVE models), and Personna
fluorescent fixtures.
Installation
Mount on a wall using four screws. Use the unit to mark the
position of the holes.
Terminal blocks in the Unit accept up to two #12 AWG
(2.5 mm
2
) wires. This allows the interface to be wired in
multiple ways. The power feed can be from a different phase
than the PRO AV DLC power.
INSIDE VIEW
FOUR MOUNTING
HOLES
FOUR SCREWS
SECURE COVER
12.5 in.
(318 mm)
3.30 in.
(84 mm)
6.10 in.
(155 mm)
Wiring overview
0-10V CONTROL FLUORESCENT ZONE/LOAD 1
0-10V CONTROL FLUORESCENT ZONE/LOAD 1
0-10V BALLAST
POWER
FROM DISTRIBUTION
PANEL
GRX-
TVI
GRX-
TVI
BALLAST
SWITCHED FLUORESCENT ZONE/LOAD 2
INCANDESCENT ZONE/LOAD 3
CONTROL UNIT
CLASS 2/PELV WALLSTATIONS
0-10V BALLAST
A GRX Interface is required for each fluorescent
dimming zone. (A 3-zone Control Unit with two
fluorescent zones and one incandescent zone is shown
as an example.)
Please note that the power feed to the Control
Unit and H
2
/L
2
of the GRX-TVI must be the same
phase!
Page 12