Specifications
DESCRIPTION
CAPACITY@
120VAC, 20A
HP•2
1
1920W/VA
HP•4
2
3840W/VA
HP•6
3
5760W/VA
POWER
Operating power: 0.20A per HP-Module, 120VAC supplied to control circuit. Input
power for load circuit(s): 120 or 277, 60Hz VAC.
32—104 ˚F (0—40 ˚C).
LOAD TYPE
DIMMED
SWITCHED
120VAC/277VAC
120 VAC/277VAC
Incandescent
16A
10A
Magnetic/electronic low voltage;
16A
10A
neon/cold cathode*
Hi-lume or ECO-10 Fluorescent
16A
16A
Fluorescent (non-dim)
— —
16A
Metal Halide
N/A
10A
Dimmed and switched hot available for each output. 50W/VA minimum load per
output.
MAXIMUM
HEAT DISSIPATION
200BTU per hour per load circuit output.
* For neon/cold cathode light sources, consult Lutron Application Note #25.
DISTRIBUTION PANEL
2 #12 AWG TYPICAL
3 #12 AWG FOR
LUTRON FLUORESCENT
DIMMING BALLASTS
DIMMING MODULE
LOAD CIRCUIT
FEEDS:
CONTROL CIRCUIT FEED:
120VAC ONLY
DIMMED HOT
NEUTRAL
BUS
20A
20A
BOOSTED
Appendix E: HP Dimming Modules
(120V control feed only)
Not for use with generator-supplied power!
HP 2•4•6 Modules increase the load capacity of a
Control Unit zone from 800W/VA to:
■
1920W/VA with the HP•2
■
3840W/VA with the HP•4
■
5760W/VA with the HP•6
■
Up to 28,800W/VA by daisy-chaining five HP•6
Modules.
HP 2•4•6 Modules can also accept 277V input load
power feeds to integrate 277V fluorescent dimming loads
controlled by Hi-lume or Eco-10 Electronic Dimming
Ballasts with 120V PRO AV Series Control Units.
Choose a mounting location
1.
Hold unit vertically.
2.
Mark and drill holes.
3.
Using the keyed upper holes for easy positioning, secure the unit to the
wall.
Please see the Instruction Sheet provided with the unit for more detailed
programming instructions.
COOLING
VENTS
6 in. AIR SPACE
IN FRONT OF
UNIT
10 in.
3 in.
■
Must be within 1000 ft. (300 m) of the Control Unit.
■
Must allow for adequate cooling. (Make sure ambient temperature is
32°—104 °F (0°—40 °C). Allow for adequate air space.
■
Must be
at least
6 ft. (1.8 m) away from sensitive electronic
equipment.
■
Must be placed where the HP 2•4•6’s slight operating noise is
acceptable.
IMPORTANT!
Leave the HP 2•4•6’s factory-installed bypass jumpers in place until you
have installed and tested the Module.
Mounting
No. OF OUTPUTS
TO LOAD CIRCUITS
MODEL
NUMBER
ENVIRONMENTAL
CAPACITIES PER
LOAD CIRCUIT
OUTPUT
6 in.
3 in.
6 in.
6 in.
3 in.
10 in.
20A
20A
Wiring Overview