FADEDIM
FADEDIM
Fade a dimmer
Syntax
FADEDIM, <intensity>, <fade time>, <delay time>, <address 1>, ..., <address n>
Parameter Description
Format
intensity
target intensity for specified dimmer
0 - 100 (percent)
fade time
time for dimmers to fade from current
intensity to target intensity
HH:MM:SS
example: 00:00:05 for 5 seconds
see
if omitted, time defaults to 0 seconds
delay time time for dimmers to delay before starting
to fade
HH:MM:SS
example: 00:00:05 for 5 seconds
see
if omitted, time defaults to 0 seconds
address
system address of dimmer to fade
[processor : link : address]
maximum of 10 address per command
see
description
Description
Fades one or more system dimmers to a target intensity using a specified fade time and after a
specified delay time.
Example
Fade processor 1, link1, MI address 0, RPM module 2, zone 3 and processor 2, link 4, D48
address 1, Vareo Bus 4, Vareo address 1 to 100% with a 1 second fade time and a 2 second
delay time
L232> FADEDIM, 100, 1, 2, [1.1.0.2.3], [2.4.1.4.1]
See Also
FLASHDIM - Flash a system dimmer
STOPFLASH - Stop flashing a system dimmer
RAISEDIM - Raise a system dimmer
LOWERDIM - Lower a system dimmer