Compatible Controls
For assistance in selecting controls, contact our LED Center of Excellence.
NOTE:
For information about Legacy product use in existing control applications, contact [email protected]
Warranty
For warranty information, please visit:
www.lutron.com/DriverWarranty
)
Lutron, Lutron, GRAFIK Eye, Hi-lume, HomeWorks,
PowPak, EcoSystem, and Quantum are trademarks of
Lutron Electronics Co., Inc., registered in the U.S. and
other countries. Energi Savr Node and myRoom are
trademarks of Lutron Electronics Co., Inc.
DALI is a trademark of ZVEI.
©2015-2016 Lutron Electronics Co., Inc.
LDE1-96W24V-E Troubleshooting
Problem
Possible Solution
LED does not illuminate • Verify that the system is wired correctly according to wiring diagram and
powered.
• Verify that the LED load is wired correctly; +LED to positive, -LED to
negative.
• Verify that the LED load is for “constant-voltage” applications with PWM
dimming.
• Verify that the LED load is compatible with the specified voltage output
of the driver.
• Lutron drivers are not for use with MR16 LED lamps.
LED does not dim
• Verify EcoSystem / DALI control wiring (E1 / DA1 and E2 / DA2) is wired
according to the instructions for digital control.
LED is flashing,
flickering, dropping out,
or has poor dimming
performance
• Verify that a compatible control is being used.
• Verify that the input voltage is within the rated limits.
• Verify that the LED load is for “constant-voltage” with PWM dimming
applications.
• Verify that the length of wires between driver and LED does not exceed
Lutron specification.
• Verify that the rated voltage is present at the driver.
• Certain types of LED loads may be incompatible.* Verify that the LED
load is within the specified wattage range of 2 W to 96 W.
• Lutron drivers are not for use with MR16 LED lamps.
LED is flashing slowly
(6 to 8 second interval)
• Verify that the LED load does not exceed the maximum specified power
rating of the driver (96 W).
• Verify that the LED load matches the specified voltage output of the
driver.
• Verify that the length of wire between driver and LED does not exceed
Lutron specification.
• Certain types of LED loads may be incompatible.*
LED output appears
dim at high-end
• Verify that rated live voltage is present at the terminal.
• Verify that the driver is operating in an environment within its ambient
temperature rating.
• Verify that the driver is not located adjacent to other heat producing
devices.
• Verify that the maximum lead length is not exceeded per Lutron
recommendation.
• Verify that the LED load is installed per manufacturer’s instructions.
• Verify that the LED load is compatible with the specified voltage output
of the driver.
Not all LED strips/
fixtures illuminate
• Verify that multiple LEDs connected to a single driver are properly wired.
• Verify that the LED load is installed per manufacturer’s instructions.
Not all LEDs on the
same strip are evenly lit
• Verify that the length of wire between the driver and LED does not
exceed Lutron specifications.
• Verify that the LED load is for “constant-voltage” with PWM dimming
applications.
• Verify that the LED load is installed per manufacturer’s instructions.
LED is brighter / hotter
than expected
• Verify that the LED load is compatible with the specified voltage output
of the driver.
* Certain constant-voltage loads may have added capacitance. Contact the Lutron LED Center of Excellence ([email protected]) for
more information about these loads.
Need Help?
Please visit the Hi-lume 1% page at www.lutron.com/europe or
call the Lutron Customer Assistance at
+44.(0)20.7680.4481
Hi-lume 1%
EcoSystem Constant-Voltage LED Driver
Compatible Controls
Compatible Controls
• EcoSystem Controls
• DALI Controls
Consult individual component installation for
more details.
Lutron Electronics Co., Inc. | 7200 Suter Road | Coopersburg, PA 18036-1299
Driver Leads
Maximum wire length between
LED driver and start of the light engine:
Wire Gauge
m (ft)
0.75 mm
2
(18 AWG)
10 (32.8)
1.0 mm
2
(16 AWG)
15 (49.2)
1.5 mm
2
(14 AWG)
20 (65.6)
2.5 mm
2
(12 AWG)
30 (98.4)
4.0 mm
2
* (10 AWG)
50 (164.0)
* To use wire gauges larger than output strain reliefs’
rated gauge of 0.75 mm
2
to 2.5 mm
2
(18 AWG to
12 AWG), connect 30 cm (12 in) or less of rated wire
from terminal through output strain relief, then connect
with the larger wire.
EcoSystem Controls
Description
Part Number
Drivers per
Control
Measured Light
Output Range
PowPak Dimming Module with
EcoSystem
RMK-ECO32-DV-B
RMM-ECO32-DV-B
32
100% – 1%
Energi Savr Node with EcoSystem
QSNE-2ECO-D
64 (2 links)
100% – 1%
HomeWorks QS with EcoSystem
LQSE-2ECO-D
64 (2 links)
100% – 1%
GRAFIK Eye QS Control Unit
QSGR-_E
64
100% – 1%
DALI Controls
Description
Part Number
Drivers per
Control
Measured Light
Output Range
Energi Savr Node with DALI
QSNE-2DAL-D
64 (2 links)
100% – 1%
GRAFIK Eye QS Wireless with
DALI
QSGRK-_D
QSGRM-_D
64
100% – 1%
GRAFIK Eye QS with DALI
(non RF)
QSGR-_D
64
100% – 1%
Quantum Total Light Management
Hub
QP2-_P_CSE-240
64
100% – 1%
HomeWorks QS / myRoom Plus
Power Module
LQSE-2DAL-D
LQRK-WPM-_D
64 (2 links)
64