© PROPERTY OF LUNDIX IT SWEDEN, ALL RIGHTS RESERVED – THE DISCLOSURE OR OTHER COMMUNICATION, COPYING, REPRODUCTION AND ANY USE WHATSOEVER IS FORBIDDEN WITHOUT THE WRITTEN AUTHORIZATION
OF LUNDIX IT.
SPC SmartBox User Manual
Revision
1.1
Page
41 of 62
Reference
2017-110
Id
Number
KNX datapoint ID. (= Parameter number in BAOS Gateway)
Name
Text
Datapoint name (imported from BAOS Gateway)
Type
Text
Datapoint type (imported from BAOS Gateway)
Value
Text
Current value. Updated in real-time.
Control
Text
Current Control value. Updated in real-time.
Command
Option menu,
Select menu
Command fields. See table below.
Supported datapoint types and possible commands:
Datapoint type
Description
Control
Value
DPT1
Binary
-
0 or1
DPT2
Binary with Control
Disable/Enable Priority
0 or 1
DPT3
Dimming with Control
Decrease/Increase Dimming
11 to 4379
DPT5
Integer 1 byte value
-
0 to 255
DPT9
Float 2 bytes value
-
-671088 to 670761
DPT12
Unsigned 4 bytes value
-
0 to 4294967295
DPT13
Signed 4 bytes value
-2147483648 to 2147483647
DPT14
Float 4 bytes value
-1000000000 to 1000000000
DPT18
Scene with Control
Activate Scene or Learn Scene
1 to 64