background image

1 8 |

P a g e

System Troubleshooting

Hard Alarms: The following give a constant audible alarm. If present, the solenoid valve is closed, 

and the 4-20, remote alarm and Wifi modules transmit the alarm.

System Display

Problem

Resolution

The system has detected 

a problem with the 

lamp.

Reset lamp protection circuit 

-unplug unit for 10 seconds.

Replace the lamp with the 

part as indicated on the silver 

label on the reactor or on the 

Maintenance parts screen.

Although the lamp is 

powered and visibly 

illuminated, due to the 

lamp’s age its UV output 

is no longer sufficient for 

proper disinfection.

Replace the lamp with the 

part as indicated on the 

silver label on the reactor or 

on the Maintenance parts 

screen.

Low UV Intensity.

Remove and clean the 

quartz sleeve and sensor.

Check water quality meets 

requirements on page 5 and 

add filtration as required. 

Replace lamp.

Wrong lamp or sensor 

installed.

Replace component with 

proper model as indicated.

The UV sensor is no 

longer communicating 

to with the system.

Ensure all modules are 

connected properly to the 

system and to each other. 

Modules can be tested indi-

vidually by plugging in one at 

a time and cycling power to 

the system.

Replace any module that is 

not detected when plugged 

directly into the controller.

A bad connection has 

been detected in the IEP 

port.

   

Missing or incorrect 

lamp key.

Ensure the lamp key 

(packed with the lamp, on 

the connector) is installed. 

Unplug and reinstall the key. 

Ensure the key part number 

matches Lamp on Mainte-

nance Parts screen.

Содержание BLACKCOMB LB5-Z12-2

Страница 1: ...tions LUMINOR Rack Mount Systems System Rated Flow Sediment Carbon LB4 Z1 LB5 Z1 8 gpm YES 10 NO LB4 Z2 LB5 Z2 8 gpm YES 20 NO LB4 Z12 LB5 Z12 8 gpm YES 10 YES 20 LBH4 Z2 LBH5 Z2 15 gpm YES 20 NO LBH4...

Страница 2: ...pply with a UV system gives you reassurance that your family will have access to safe drinking water throughout your entire home with no chance of microbiological contamination This is chemical free p...

Страница 3: ...1 BLACKCOMB6 1 Controllers 14 BLACKCOMB5 1 BLACKCOMB6 1 Power up Sequence 14 BLACKCOMB5 1 Operational Screens 15 BLACKCOMB6 1 Operational Screens 16 Lamp Countdown Sequence 16 System Service Suggested...

Страница 4: ...vice instructions if required 7 Do not use this system for any purpose other than what it was intended for Misuse of this system could potentially cause harm to the user or others 8 Your system is int...

Страница 5: ...required will depend on parameters being treated Hardness 7 gpg 120 mg L if hardness level is 7 gpg or slightly below the quartz sleeve must be cleaned periodically in order to ensure effi cient UV p...

Страница 6: ...OMB rack mount UV system is designed as a do it yourself DIY system with a single inlet and outlet port Unpack the system and ensure all the components are included in the box Your system is shipped w...

Страница 7: ...s until the pump stops This is known as the cycle time 4 Then using a container of known volume preferably in US Gallons open the faucet or tap nearest the pressure system and measure the amount of wa...

Страница 8: ...ng plate 4 screws for a single filter model and 8 screws for a double filter model Step 3 Carefully lower the filter head or heads from the rack assembly and rotate 180 de grees Reassemble onto the ra...

Страница 9: ...idue on the sleeve and lamp which can ultimately block the UV light from getting to the water Carefully slide the sleeve into the reactor until you can feel it hit the opposite end of the reactor Alig...

Страница 10: ...the system The most common leak is from the o ring not making a proper seal on the reactor For new installations review steps 6 and 7 For older systems drain the reactor remove the o ring dry it and r...

Страница 11: ...land nut and turn the connector approximately turn to lock the connector to the gland nut as in Figure 10 Figure 9 Lamp Key Installation Figure 10 LUMI Loc Connector Step 14 Tighten the captive ground...

Страница 12: ...y require periodic cleaning At a minimum the quartz sleeve should be cleaned on an annual basis The following steps outline a basic clean ing procedure Step 1 If a by pass assembly is installed shut t...

Страница 13: ...slowly out of the sensor port Step 6 Holding the sensor in your hand wipe the flat portion sensor face of the sensor with isopropyl alcohol using a clean lint free cloth Step 7 Replace sensor followin...

Страница 14: ...ystem s performance in addition to pro viding any applicable fault messages and system diagnostics The controllers used in both the BLACKCOMB5 1 and BLACK COMB6 1 are identical The difference is that...

Страница 15: ...reens by pressing the button located on the front of the controller BLACKCOMB6 1 Operational Screens On systems with the UV monitor the system will display the same screens as on the BLACK COMB5 1 exc...

Страница 16: ...dible chirp Past the zero day threshold the LED or display screen changes to solid red with a continuous buzzer BLACKCOMB6 1 BLACKCOMB5 1 BLACKCOMB4 1 At any point during this sequence the audible chi...

Страница 17: ...stems After the lamp is expired it must be replaced with the same part number as indicated on the Maintenance Parts screen or on the label on the reactor With the system powered down re move and disca...

Страница 18: ...n the reactor or on the Maintenance parts screen Low UV Intensity Remove and clean the quartz sleeve and sensor Check water quality meets requirements on page 5 and add filtration as required Replace...

Страница 19: ...extreme situations elevated water temperature or the fluctuation in temperature can lower the output of the UV lamp In these cases or if the elevated water temperature is a nuisance LUMINOR recommends...

Страница 20: ...rating is 240VAC 50 60Hz 30VDC 2A On a non monitored system the solenoid will only close on a lamp failure error On a monitored system the solenoid is closed when the UV level drops below 50 Also not...

Страница 21: ...suffix i e LB5 Z1 3 Australian New Zealand AS NZ 3112 4 suffix i e LB5 Z1 4 Lamp Power Watts 20 standard output lamp 45 high output lamp Power Watts 23 21 230V 57 48 230V Replacement Lamp RL 420 RL 4...

Страница 22: ...OR will not be liable for any costs of removal installation transportation or any other charges which may arise in connection with a warranty claim Products which are sold but not manufactured by LUMI...

Страница 23: ...TO THE EXTENT ALLOWED BY APPLICABLE LAW ANY AND ALL EXPRESS OR IMPLIED WARRANTIES NOT SET FORTH HEREIN ARE WAIVED AND DISCLAIMED INCLUDING ANY IMPLIED WARRANTY OF MERCHANT ABILITY OR FITNESS FOR A PA...

Страница 24: ...luminating technologies for life 80 Southgate Drive Unit 4 Guelph Ontario CANADA N1G 4P5 P 519 837 3800 TF 855 837 3801 F 519 837 3808 info luminoruv com www luminoruv com PN 910114 Version Date 12 20...

Отзывы: