ULT20 - User’s manual_rev.A
55
5.7.4.5 Registers 7800 – 7949 and 8200 – 8498
32-bit and corresponding to them 16-bit registers with configuration parameters. The
address given in address field is the address for 32-bit variables, in brackets there is
address to access data placed in two subsequent 16-bit registers.
Address
(registers
32 bit
float)
Address
(Value in 2
registers
16-bit)
Symbol
Acceptable values Default
Description
Parameters of analog output
7800
8200
AnIn Lo
-99999...999999
0
Value controlling analog output for which
the output signal must reach minimum
value.
7801
8202
AnIn Hi
-99999...999999
5
Value controlling analog output for which
the output signal must reach maximum
value.
7802
8204
AnManVal
0...24
0
Value of analog output current during
manual control.
Configuration of alarms
7803
8206
OverLo Al
-99999...999999
1
Alarm no. 1 – lower control value changing
the state of relay contacts.
7804
8208
OverHi Al
-99999...999999
3
Alarm no. 1 – upper control value
changing the state of relay contacts.
7805
8210
OverLo Al
-99999...999999
1
Alarm no. 2 – lower control value changing
the state of relay contacts.
7806
8212
OverHi Al
-99999...999999
3
Alarm no. 2 – upper control value
changing the state of relay contacts.
Minimum and maximum displayed value
7807
8214
Over Lo
-99999...999999
-99999
Minimum value of displayed main value
acc. to
PAR1
. Lower overrun is displayed
below this value.
7808
8216
Over Hi
-99999...999999 999999
Maximum value of displayed main value
acc. to
PAR1
. Upper overrun is displayed
below this value.
7809
8218
Over Lo
-99999...999999
-99999
Minimum value of displayed additional
value acc. to
PAR2
. Lower overrun is
displayed below this value.
7810
8220
Over Lo
-99999...999999 999999
Maximum value of displayed additional
value acc. to
PAR2
. Lower overrun is
displayed below this value.
Binary output
7811
8222
Pulse K
0...999999
1
Pulse weight for counter binary output.
When counter reaches the specified value
a pulse is generated at binary output.