INFRATHERM 

pyrometer IS 50-LO/GL 

 

 

17

5 Electrical 

installation 

 
The 

INFRATHERM 

IS 50-LO/GL is powered by 24 V ± 25 % (18 … 30 V DC). When connecting it to the power supply 

ensure correct polarity. The power consumption (in this case 4 - 20 mA) is also the measuring signal. The instrument 
don’t need any time for starting or preheating and is immediately ready for operation. To switch off the instrument, inter-
rupt the instrument’s power supply. 
 
To meet the electromagnetic requirements (EMV), a shielded connecting cable must be used. The shield of the connect-
ing cable has to be connected only on the pyrometer’s side. On side of the power supply (switch board) the shield must 
be open to avoid ground loops. 
 

 

5.1 

Connector assignment for the converter 

 
 Connector: 
 

3 pole flange plug; series 723 (Franz Binder GmbH & Co., Germany) 

 
 

 Pin 1 

(white) 

+24 V ± 25 % 

Pin 2 

(brown) 

0 V 

Pin 3 

(black) 

shield 

 
 
 

5.2 

Connection of additional analyzing devices 

Additional analyzing instruments, for example a LED digital display instrument only needs to be connected to a power 
supply and the analog outputs from the pyrometer (display devices from IMPAC have a built-in power supply for 2 wire 
pyrometers and don’t need a separate power supply). Another Instruments like a controller or printer can be connected to 
the display in series. 
 
 

 

+

+

white 

brown 

Signal processor 

4 ... 20 mA 

Power supply 
24 V DC 

Display with  
power unit 

 

 
 

6 Mechanical 

installation 

 

6.1 Overview 

 

 

 
 
 
 
 

Содержание Impac IS 50-LO/GL

Страница 1: ...IS 50 LO GL INFRATHERM Pyrometer Betriebsanleitung User Manual IMPAC Spezialist f r ber hrungslose Temperaturmessung IMPAC Specialist in non contact thermometry www imaxsun com...

Страница 2: ...of additional analyzing devices 17 6 Mechanical installation 17 6 1 Overview 17 6 2 Converter 18 6 3 Fibre optical head 18 6 3 1 Ambient temperature 18 6 3 2 Serial number 18 6 4 Minimum bending radiu...

Страница 3: ...C Infrared GmbH have a warranty of two years from the invoice date This warranty covers manufacturing defects and faults which arise during operation only if they are the result of defects caused by I...

Страница 4: ...e must be within the limits of the full temperature range and must have a minimum span of 51 C Emissivity 5 100 set via emissivity control inside the pyrometer Response time 1 s set ex works Accuracy...

Страница 5: ...in a permanent readable condition 4 1 General Each person working with the pyrometer must have read and understood the user manual before operation Also this has to be done if the person already used...

Страница 6: ...n side of the power supply switch board the shield must be open to avoid ground loops 5 1 Connector assignment for the converter Connector 3 pole flange plug series 723 Franz Binder GmbH Co Germany Pi...

Страница 7: ...ble The fibre optic connectors are equipped with a special sealing ring to protect the connection against penetra tion of liquids Attention The light guide end of the fibre optic cable as well as the...

Страница 8: ...on from the measured object which passes through the lens and is then converted to an electrical signal The measured object may be at any distance from the pyrometer However the farther the measured o...

Страница 9: ...erature The emissivity setting of the pyrometer has to be adjusted accordingly Typical emissivity values are listed below Measuring object Emissivity at 0 8 1 1 m molten glass 96 Set up examples at th...

Страница 10: ...e 4 20 mA current output of the pyrometer This is especially important if the temperature control of your system i e oven or furnace temperature is dependent on the output signal from the pyrometer 8...

Страница 11: ...al head 11 2 Accessories 3 820 650 Connection cable length 5 m 3 820 660 Connection cable length 10 m 3 820 670 Connection cable length 15 m 3 820 680 Connection cable length 30 m On request Other len...

Отзывы: