Operating Manual V25/09.2019
Ventus / Ventus-X / V200A
Chapter 12 Configuration and Test
24
Give the device a name of your choice. You will be able to change it later at any time.
Select
„ Ventus / Ventus-X / V200A-UMB“ in the device selection list
Enter the device address (device ID) into the field next to the device selection list
This is the address over which the UMB-ConfigTool.Net will later communicate with the
device.
Save your entries. You will get back to the overview of your workspace.
Select the sensor that you have just set up.
Note:
The default address on delivery is 1. For the first commissioning therefore device address
1 has to be selected. If the device address is changed in the configuration settings, the address
that is saved in the UMB-ConfigTool.Net has to be changed accordingly.
Note:
If several
Ventus
are used in one UMB network, each one must have its unique ID. It
makes sense to start with 1 and count upwards.
12.2.2 Device settings
All
Ventus
parameters are shown in the device settings. Unchangeable settings have a grey
background, see Figure 10.
Figure 10: Device settings
12.2.3 Device identification
Device ID:
Device ID
default setting 1; to futher devices assigne IDs in ascending order
Device description:
For identifying the devices a description like the location can be
entered
12.2.4 Device parameters
Baudrate:
Transfer rate of the RS485 interface
default setting 19200 Baud; DO NOT change if used with ISOCON-
UMB.
Содержание 8371.UA01
Страница 1: ......
Страница 2: ...Operating Manual V25 09 2019 Ventus Ventus X V200A 2 ...
Страница 29: ...Operating Manual V25 09 2019 Ventus Ventus X V200A Chapter 12 Configuration and Test 29 Figure 15 Channel list ...
Страница 30: ...Operating Manual V25 09 2019 Ventus Ventus X V200A Chapter 12 Configuration and Test 30 Figure 16 Data query ...
Страница 65: ...Operating Manual V25 09 2019 Ventus Ventus X V200A Chapter 20 Appendix 65 0XM11 CR LF ...
Страница 76: ......