10.4 Function Configuration
Alarm configuration
·Alarm threshold: HH, HI, LO, LL
are the upper limit, upper limit,
lower limit, lower and lower l imit
a l a r m r e s p e c t i v e l y , a n d t h e
subsequent value is the corresp-
onding alarm threshold, when the
actual data exceeds the sum or
difference of the corresponding
limit and hysteresis Only then will
the alarm signal be generated or
eliminated.
Function
configuration
Alarm configuration
Communication configuration
Output configuration
·Alarm hysteresis: The alarm hysteresis is to prevent the instrument from repeating
multiple alarms near the alarm point. For example, the set range is 0 ~ 100, the high
alarm point is 80, the low alarm point is 20, and the alarm hysteresis is 5.0. %, When the
high alarm occurs, the instrument will cancel the alarm when the measured value is less
than 80-100 * 5% = 75. Similarly, when the low alarm occurs, the measured value of the
instrument is greater than 20 + 100 * When 5% = 25, the alarm is cancelled.
Communication configuration
The instrument supports communication operation with the host computer, real-time
monitoring of the instrument, etc. The communication configuration is used to set the
parameters such as the communication mode, address, and baud rate of the machine.
The mode is divided into PC and printer. When the mode is "PC", the baud rate can be
selected, and when the mode is "Printer" At this time, the baud rate is not selectable, and
the stop bit and verification can be the default (need to correspond to the software setting
of the host computer). The communication address is selectable from 001 to 255. When
forming the same communication network, the communication address of the instrument
is not allowed to be repeated.
Output configuration
·Alarm contact: relay number, such as contact 01 represents relay 01. When the signal
value exceeds the alarm setting value, the relay corresponding to the contact number will
act and the contact will close. If "None" is selected, it means that the relay will not operate
regardless of whether the signal exceeds the limit, but there are still alarm records in the
alarm list.
Contacts:
Contacts:
Contacts:
Contacts:
No
No
Function configuration
Alarm Settings
Communication configuration
Output configuration
Return
difference
The way
Stop bit
Baud rate
Bit
Machine Address
Check odd
Aisle
Effect
Range
Signal sourcege
Guild
Type
Unit
Quit
Quit
Quit
Quit
24
EN
7
0
1
7
8
7
2
.0
6
0
9
/2
0
1
8
C
H
/E
N