Lucent Technologies Lineage
®
2000 50A Ferroresonant Rectifier J85502B-1
Issue 6 May 1999
Spare Parts and Replacement Procedures 8 - 19
Main
Transformer (T1)
1. Disconnect lead 1, 2, or 3 from contactor K3.
2. Disconnect ac leads from TB1 at L1, L2, and L3.
3. Remove the diode heat sink assembly (see “Diode Heat
Sink Assembly”) and disconnect the diode pigtail
connections of leads 6 and 8. (See “Rectifier Diode Test
and/or Replacement.”)
4. Disconnect lead 5 from dc capacitor common negative
terminal.
5. Disconnect leads 9 and 10 from C5.
6. Disconnect P2 header connector from the CM1 option
board, leads 11 and 12.
7. Remove the L1 inductor from the rear compartment.
8. Remove the nut holding the top angle bracket to the center
mounting plate.
9. Remove the two nuts and one bolt that hold the top angle
bracket to T1.
10. Loosen the remaining five nuts that hold the center
mounting plate to the frame.
11. Slide the center mounting plate forward.
12. Remove the top angle bracket by first pivoting it upward
above the front threaded stud and then sliding it out to the
left.
13. Remove the two nuts that hold T1 to the lower angle
bracket.
Notes
This procedure assumes that the rectifier has been
removed from the bay and that all covers of the rectifier
have been removed.
Lead numbers refer to T1 unless otherwise noted.