Lucent Technologies Lineage
®
2000 50A Ferroresonant Rectifier J85502B-1
8 - 16 Spare Parts and Replacement Procedures
Issue 6 May 1999
2. Remove the quick-disconnect connectors from the CA1
board.
3. Remove the CA1 board from its support standoffs, one at a
time, by pushing in on the spring-loaded tabs while pulling
out on each corner of the board.
4. When reversing the procedure for reinstallation, make sure
the board is fully seated on the support stand-offs in locked
position.
Thyristor (Q1)
1. Move TB3 aside by removing the two mounting nuts, but
do not remove leads.
2. Remove the CM1 option board (see “Replacing CM1
Option Board).
3. Remove CBA1 bracket assembly from frame by removing
its two mounting screws. Move CBA1 bracket out of the
way.
4. Remove thyristor Q1 mounting bracket by removing two
mounting nuts from studs on the wall.
5. The wire(s) from Q1 are tied to the center mounting plate.
Loosen the wire tie on the plate by removing its nut.
6. Remove Q1 mounting nut.
7. Noting their connection positions, unsolder leads from Q1.
Diode Heat Sink
Assembly
1. Remove the upper (common) lead from the heat sink that
goes to dc capacitor C1 by removing the terminal nut.
2. Carefully push T1 Lead 7 just enough to access heat sink.
Use caution to avoid bending the wires entering T1.
3. Remove the two mounting screws that secure heat sink.
4. Lift sink out and rotate clockwise to gain access to back
side.
5. The diodes can now be tested or removed. (See “Rectifier
Diode Test and/or Replacement.”