Spraying ratio
The spraying ratio defined in the menu is only valid in manual mode and
in the “auto extern” running mode. Example: 01.30min interval duration
and 20% spray rate results in a spraying time of 18sec.
In the running mode “auto internal” or “auto VPD” the spraying ratio is
calculated at the beginning of the interval on the basis of the rated values
and the position of the sensor values in the con-trol range.
Air-cleaning
The system sprays in the set air-cleaning interval. If the “Air-cleaning”
function is activated, “Air-cleaning” appears in the status display.
Note: The breaking time in the air cleaning interval should be much
longer than the set spraying time, so that the influence on the climate
remains small.
Note: In automatic mode, the system only sprays for air cleaning if there
are no further spraying requirements for the duration of the set breaking
time (from a climate computer or on the basis of the sensor values).
Timer
The timer switches the system on at the starting time and off again at the
stopping time. When the stopping time is reached, the sta-tus display
shows “System waits”. The timer function key also flashes.
Note: In order to be able to use the “Timer” function, the time must first
be set under “Adjust time” in the “System-parameter” menu.
5.7.5 Operating principle of temperature- and humidity-control LCS
controller
The following illustrations show the effects of the sensor values on the spraying ratio. Depending on the position
of the values in the control ranges, the spraying ratio is calculated as shown.