8 Residual risks
•
Sharp edges & corners
There is a substantial risk of injuries due to sharp edges and corners of coil and casing. Make
sure to wear reliable protection during any handling of the unit and maintenance activities.
•
Drip tray
Ensure the drip tray is empty before lowering or disassembling. The weight of any leftover water
or ice could injure the operator if the drip tray fell open accidentally.
•
Side plates
Removable side plates may only be opened by qualified staff. Ensure the side plates are
properly secured after closing.
•
Fans
Rotating fans can cause injuries to fingers. Never operate fans without the mounted protection
grid and take care of loose clothing. Switch power off before any maintenance.
•
Electrics
Power must be switched off before any work or maintenance on electrical parts of the unit.
Secure the unit against unintentional switching on.
•
Burns or frostbite
(Distributor) tubes can be extremely cold, whereas defrost heater elements can get very hot.
Use reliable protection.
•
Working fluids
Working fluids might be toxic and/or flammable. These substances may only be handled by
qualified staff while taking all necessary precautions and following any applicable regulations.
•
Fan vibrations
Continuous fan vibrations can cause material failure and hence a risk of injury or damage due to
loose parts. Therefore vibrations must be reduced to a minimum at all times.
9 Troubleshooting
Fault
Possible cause
Required action
Fan motor not functioning
No power supply
Check/restore power supply.
No control signal (EC motors)
Check/restore control signal.
Fan blade blocked
Remove obstruction.
Fan motor burnt
- Check for fan blade obstructions.
- Check thermal protection device.
- Replace fan motor.
Excess motor noise
Defective fan motor bearing
Replace fan motor.
Excess vibrations
Loose fan fasteners
Tighten fasteners.
Unbalanced fan blades
Replace fan blades.
Insufficient capacity
Heat exchanger coil dirty/blocked
Clean coil.
Coil partly blocked by solid ice
- Check defrost cycle settings.
- Check defrost heaters.
- Perform 100% coil defrost to remove all ice.
Fans not (properly) functioning
Check fans.
Refrigerant supply/pressure insufficient
Restore refrigerant supply/pressure to reference values.
Refrigerant leakage
Refrigerant containing parts damaged
- Stop fans.
- Close refrigerant supply.
- Repair leak.