SV-iS7 CANopen Manual
35
Code
Description
Keypad
Display
Setting Range
Factory
Default
Type/Units
COM-53
Keypad Addr of the RPDO Data
to be read from CANopen
Master
Para Control -3 0x0000-0xFFFF
0x0000 0xXXXX
Hex
COM-54
Keypad Addr of the RPDO Data
to be read from CANopen
Master
Para Control -4 0x0000-0xFFFF
0x0000 0xXXXX Hex
COM-94 Reflect parameter on Option
Comm Update
“No”
“Yes”
“No” -
PRT-12
Set up inverter operation in
the event of Lost Command
Lost Cmd Mode
"None"
"Free-Run"
"Dec"
"Hold Input"
"Hold Output"
"Lost Preset"
"None"
-
PRT-13
Set up the time for the Lost
Command
Lost Cmd Time
0.1~120.0
1.0
0.0 sec
PRT-14
Set up the speed of Lost
Preset
Lost Preset F
0.00
0 Hz/Rpm
7.2
Description on the Basic Field Bus Parameters
7.2.1 COM 07 FBus ID
The allowable setting range in the inverter is 0~127. However, 0 is not used as a station No. in CANopen. If set to
o, the ERR LED will blink in the CANopen Option. (See Section 3.2)
7.2.2 COM 09 FBus LED
These parameters control the LEDs on the CANopen board.
0Bit: CPU LED
1Bit: ERR LED
2Bit: NODE LED
3Bit: BUS LED