SV-iS7 CANopen Manual
20
Transition Event Action
5
On receiving Disable Operation command
The command to maintain current inverter
status is not accepted. I.e., stop
command is not accepted.
6
On receiving Shut Down command
If motor has been running, conduct Free
run stop
7
On receiving Disable voltage command
None
8
On receiving Shut Down command
Conduct Free run stop
9
On receiving Disable voltage command
Conduct Free run stop
10
On receiving Disable voltage command or
Quick Stop command
Conduct Free run stop
11
On receiving Quick Stop command
Reduce speed at the reducing time setup
in the Quick Stop
12
On receiving Disable voltage command
Conduct Free run stop
13
When the inverter tripped
Conduct Trip sequence
14
Automatic change
Conduct Trip sequence
15
On receiving Reset command or Trip is
released
Change to Switch on disable state
16
On receiving Enable operation command Motor runs again
6.1.2 CiA
402
SDO
6.1.2.1
Error codes (Object: 0x603F)
Index
: 0x603F
When the inverter is tripped, this SDO is used to identify the type of the trip.
The table below presents the Error code No. for response to the inverter trip.
Fault Code Number
Description
0x0000 None
0x1000 UNDEFINED
0x2220 Inverter
OLT
0x2310 OverCurrent1
0x2330 Ground
Trip
0x2340 OverCurrent2
0x3130
In Phase Open
0x3210 Over
Voltage
0x3220 Low
Voltage
0x4000 NTC
Open