51
Error
code
Error message
Description
Action
0x0E0027
DC current regis-
tration
Failure of DC current con-
verter
Contact the Service.
0x0E0028
Invalid country of
use
Country code is missing
Input the country code at
the initial installation. (It can
be changed only service
personnel.)
0x0E0029
Power supply fault
1
ENS function fault
Contact the Service.
0x0E002B Insulation
1
Insulation measurement
fault
Upon entry into the
ACTIVATION phase, the
acknowledge signal of the
REFU insulation measuring
instrument (at digital input
X17 pin 8) must at LOW
level. If this is not the case,
the inverter emits the “Insu-
lation 1” error.
Check the insulation of the
system.
0x0E002C Insulation
2
Insulation measurement
fault
Insulation measurements
are taken in the ACTIVA-
TION phase.
If the ISO measuring in-
strument (at digital input
X17 pin 8) fails to give posi-
tive feedback after the
maximum measuring time
has elapsed, there is an
insulation fault.
Where the LSPV 500K +
630K is concerned, the in-
sulation measuring instru-
ment is polled even during
ongoing operation.
Check the insulation of the
system.
0x0E002D
AC current
measurement
Failure of DC current con-
verter
Contact the Service.
0x0E002F
DC voltage 1
Different DC voltages at
stack 1 and stack 2
The DC link voltages at WR
stack 1 and WR stack 2
must be identical.
Allowed difference: 30V.
Check the function and
contact the Service.
0x0E0031
Lightning protec-
tion
Fault through lightning pro-
tection element
Check the lightning protec-
tion. Exchange if neces-
sary. Reset.