23
WARNING
Live PV strings can be under lethal voltages.
⇒
Before connecting the PV strings, verify that the open circuit voltage
does not exceed 50 V.
•
The DC connection is effected with MC4-plugs and sockets Ensure that you use DC
connectors which are suitable for the particular cable diameter. If you use connectors
which are not suitable for the particular cable diameter, the protection class of the de-
vice may fall below IP65.
•
Whenever it is switched on, LSPV inverter automatically checks the insulation of the
PV generator. If the insulation is defective, LSPV inverter switches off automatically. In
this case, it is absolutely mandatory that the insulation fault of the PV generator be re-
paired before the PV generator is connected to LSPV inverter.
•
Be absolutely sure to verify proper polarity when connecting the PV strings. Any inap-
propriate connection of individual strings may damage the module strings. The LSPV
inverter is protected by an integrated polarity reversal protection diode. Protect the
connectors such that they cannot be pulled off inadvertently.
•
Close unused connectors with plugs. If you fail to do this, the protection class of the
device may fall below IP65.
•
The connection has to be strictly done according to chapter 2.5 Solar Inverter DC
Connector of the operating instructions. By non-observance the dc-disconnector can
be destroyed.
3.13 DC Connecting Line
Please note the following information (plug type, cross section) regarding the DC power cable
Denomination
Type
Item No.
MultiContact
Diameter wire insulation
in mm
Cable cross section in
mm²
Connector plug
PV-KST4/6I-UR
32.0015P0001
3 -6
4 - 6
Connector plug
PV-KST4/6II-UR 32.0017P0001
5,5 - 9
4 - 6
Connector socket
PV-KBT4/6I-UR
32.0014P0001
3 - 6
4 - 6
Connector socket
PV-KBT4/6II-UR 32.0016P0001
5,5 - 9
4 - 6
To attach the crimp contacts on the site, you might acquire the pliers, type PV-CZM -19100 by Mul-
tiContact.
Note:
In order to ensure the degree of protection IP65, plug connectors and
power supply connection cable must be matched to each other and
all unused connectors shall be fitted with blanking plugs. We suggest
to use only original components of MultiContact! Please take notice of