Chapter 7 Program Example
7 - 1
Chapter 7 Program Example
7.1 Example of communication with XBL-PMEC
This example shows a program that is installed on No. 0 slot of XGT No. 0 base, sending and
receiving data to Smart I/O module(Station Number 3 and 4) and Extended Smart I/O
Pnet(Station 6).
[Figure 7.1.1] I/O Structure and Sending/Receiving Data
Slave
Master
Station No.
Module name
Mode
Read Area
Save Area
Size (byte)
4
GPL-TR2A
Sending
M0000(2byte)
-
2
3
GPL-D22A
Receiving
-
M0200(2byte)
2
6
XPL-BSSA
XBE-TN32A
Sending
M0000(4byte)
-
Sending(22byte)/
Receiving(20byte)
XBE-DC32A Receiving
-
M0311(4byte)
XBF-AD04A Receiving
-
M0313(8byte)
XBF-DV04A
Sending
M0302(8byte)
-
XBF-DC04A
Sending
M0306(8byte)
-
XBF-RD04A Receiving
-
M0317(8byte)
XBE-RY16A
Sending
M0310(2byte)
-
[Table 7.1.1] High-Speed Link Sending/Receiving Map
In the table above, XBC-H type main unit sends 2 byte data in M0000 area to GPL-TR2A and
22 byte data in M0300~0310 area to XPL-BSSA and saves 2 byte (16 points) input data of
GPL-D22A in M0200 area of XBC-H type main unit and 20 byte input data of XPL-BSSA in
M0311~3020 area of XBC-H type main unit.