Chapter 2 Specifications
2 - 1
Chapter 2 Specifications
2.1 General Specifications
General specifications of XGT series are as specified below in Table 2.1.
No.
Item
Specification
Related specifications
1
Operating
temp.
0
℃∼
+55
℃
-
2
Storage temp.
-25
℃∼
+70
℃
-
3
Operating
humidity
5
∼
95%RH, no dew allowed
-
4
Storage
humidity
5
∼
95%RH, no dew allowed
-
5
Vibration
immunity
For discontinuous vibration
-
Frequency
Acceleration
Amplitude
Number
IEC61131-2
5
≤f< 8.4
㎐
-
3.5mm
Each 10 times in
X,Y,Z directions
8.4
≤f≤150
㎐
9.8
㎨
(1G)
-
For continuous vibration
Frequency
Acceleration
Amplitude
5
≤f< 8.4
㎐
-
1.75mm
8.4
≤f≤150
㎐
4.9
㎨
(0.5G)
-
6
Impact
immunity
* Max. impact acceleration: 147
㎨
(15G)
* Authorized time: 11
㎳
* Pulse wave : Sign half-wave pulse
(Each 3 times in X,Y,Z directions)
IEC61131-2
7
Noise
immunity
Square wave
impulse noise
AC:
±
1,500V
DC:
±
900V
Test specification of
LS Industrial Systems
Static electric
discharging
Voltage : 4kV
(contact discharging)
IEC 61131-2,
IEC 61000-4-2
Radiation electromagnetic
field noise
80 ~1,000MHz, 10 V/m
IEC 61131-2,
IEC 61000-4-3
Fast
Transient
/burst
noise
Class
Power
module
Digital/Analog I/O
communication interface
IEC 61131-2,
IEC 61000-4-4
Voltage
2kV
1kV
8
Ambient
conditions
No corrosive gas or dust
9
Operating
height
2,000m or less
10
Pollution level
2 or less
11
Cooling type
Natural air cooling
Table 2.1 General Specifications
Remark
1) IEC(International Electrotechnical Commission):
An international nongovernmental organization which promotes internationally cooperated standardization in
electric/electronic fields, publishes international standards and manages applicable estimation system related with.
2) Pollution level: An index indicating pollution level of the operating environment which decides insulation
performance of the devices. For instance, Pollution level 2 indicates the state generally that only non-conductive
pollution occurs. However, this state contains temporary conduction due to dew produced.
Содержание XBL-PMEC
Страница 50: ...Chapter 5 PROFICON Setting 5 18 Figure 5 4 8 Network topology collected and composed...
Страница 84: ...Chapter 7 Program Example 7 12 Figure 7 3 3 Screen of communication module setting...
Страница 91: ...Chapter 8 Troubleshooting 8 3 8 5 Troubleshooting 8 5 1 Connection error on PROFICON XG5000...
Страница 99: ...Appendix A 7 A 4 External Dimensions Unit mm XBL PMEC XBL PMEC...