HARDWARE INSTALLATION GUIDE
Inspect the UPS upon receipt . The packaging is recyclable; keep it for reuse or dispose of properly .
Safety Information
Information presented here is vital to all personnel . Please read all Safety information .
Storage and Transportation
Please handle the UPS and associated equipment with extreme caution since a high amount of energy is contained in the
batteries . Always keep the unit in an upright position as marked on the packaging, and never drop the unit .
Adhere to the following instructions if the UPS is not installed immediately:
• Store the equipment as is in its original packing and shipping carton .
• Do not store in temperatures outside the range of 5°F to 77°F (-15°C to +25°C)
• Ensure that the equipment is fully protected from wet or damp areas and from moist air .
In order to maintain the batteries, the UPS should be recharged every 6 months for at least 8 hours .
If flammable substances such as gases or fumes are present, or if the room is airtight, a hazardous situation may exist in which
no electrical equipment should be operated .
The instructions in this manual explain how to install the UPS safely . Not acknowledging such electrical hazards may be fatal –
keep this manual for future reference .
Environment
Ensure that all environmental concerns and requirements are met according to specifications listed in this document, otherwise
the safety of installation personnel cannot be guaranteed, and the unit may malfunction .
Ensure that you remember the following when locating the UPS system and battery options:
• Avoid extremes of temperature and humidity . Maximum battery life can be attained with a recommended temperature
range of 59°F to 77°F (+15°C to +25°C)
• Provide protection for the equipment from moisture .
• Space and ventilation requirements must be met . Ensure there are 4 inches (100mm) behind and 2 inches (50mm) on
the sides of the UPS for proper ventilation .
• Ensure that the front of the UPS remains clear for user operation .
WARNING!
It is strongly recommended that the UPS cabinet not be opened as components
have very high voltage and touching those components may be fatal. Only a
qualified technician or authorized agent may service the unit.
The UPS unit’s output receptacles carry live voltage even when not connected to
an input voltage source. The UPS has its own internal energy source.