Lowell UPS9 Series Manual
Pg. 8
Communication Connections
To allow for unattended UPS shutdown/start-up and status monitoring, connect one end of the communication cable to the
USB/RS232 port and the other to the communications port on your PC or server . With the monitoring software installed, the
UPS can be scheduled for shutdown/start-up and monitoring of the UPS status through the PC or server .
•
RS-232 Communications
The RS-232 interface uses a 9-pin female D-sub connector . Information provided includes data about utility, load and the
UPS . The interface port pins and their functions are identified in the following table:
•
SNMP Communications Option
The UPS provides an intelligent slot for internal or external network card . This special intelligent network card can be compat-
ible with popular software and hardware found on the web and in operating systems . It can support operating systems such
as HP Open View, IBM Netview, SUN Netmanager, etc . This enables the UPS to provide instant UPS and power information
over the network . Please contact your reseller for additional details .
Emergency Power Off (EPO) Port
A customer supplied switch located remotely can be used to close the EPO connection and allows the UPS output receptacles
to be switched off . Since the EPO shuts down the equipment immediately, orderly shutdown procedures are not followed by any
power management software . The UPS will have to be manually restarted in order to regain power to the outlets on the UPS .
Keep Pin 1 and Pin 2 closed for UPS normal operation . To activate EPO function, open the wire between Pin 1 and Pin 2 .
PIN #
FUNCTIONS
1,4,6,7,8,9
Reserved
2
UPS transmit
3
UPS receive
5
Ground
It’s in closed status for UPS normal operation .