©2021 Lowell Manufacturing Co. UPS9A Series (X-Rev 8/13/20)
Pg. 11
5.
Stabilize the connector to the UPS and the battery pack(s) by fixing screws as shown below diagram.
6.
Connect internal battery connector and put the front panel back to the unit.
Step 2: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
l
For UPS9A models: The power cord is attached to the UPS. The input plug is a NEMA 5-15P for 1000 and 1500
models, NEMA 5-20P for 2000 model and NEMA L5-30P for 3000 model. To reduce the risk of fire, connect only
to a circuit provided with (@) a maximum branch circuit overcurrent protection in accordance with the National
Electrical Code, ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1.
Model
(@)
UPS9A-1000
20A
UPS9A-1500
20A
UPS9A-2000
20A
UPS9A-3000
40A