OPERATIONAL STATUS
– During normal operation, if the user does not press the navigation keys to view values, the text bar indicates the starter's status.
– The possible statuses are given in the following table, with their explanations:
REMOTE DISPLAY UNIT
– All the information available on the display of the ADXL soft starter can be viewed remotely on the remote display unit Lovato EXCRDU1.
– EXC RDU1 is provided with backlit graphic LCD display touch screen and built-in RS485 communication port, which allows the connection to soft starters ADXL series equipped with the optional RS485 card, code
EXC 1042.
– EXC RDU1 is compatible with 96x96mm holes.
– Protection degree IP65 and 4X.
– EXC RDU1 is provided with connection cable 3mt length.
– With EXC RDU1 is possible to command the start and stop of the motor, access to the setup menu, modify the parameters of the soft starter and monitor the status and the electrical variables.
– EXC RDU1 can control up to 32 soft starters ADXL series in contemporary.
– The maximum distance between EXC RDU1 and the more distant soft starter can reach 600mt.
STATUS DISPLAY DESCRIPTION
Line absent NO POWER No power on terminals L1-L2-L3.
Starter ready READY Power present, soft starter ready to run.
Start delay xx DELAY XX Delay applicable to the current start command. A countdown displays.
Start kick KICK.STA Kickstart in progress.
Acceleration ramp ACC. RAMP Motor acceleration ramp in progress.
Current limit CURR. LIM. Current limitation during acceleration ramp.
Torque limit TRQ. LIM. Torque limitation during acceleration ramp.
Run RUN End of acceleration ramp, full voltage to motor via SCR.
By-pass closed BYPASS End of acceleration ramp, full voltage to motor via bypass.
Deceleration ramp DEC. RAMP Motor deceleration ramp in progress.
Protections disabled INH. PROT. Protections disabled by external command.
Freewheel FREEWHEEL External free-range stop command.
Preheating PREHEAT Motor winding preheating enabled.
Alarm ALARM One or more alarms present.