Pollution degree environment Degree 2
Overvoltage category 3
Measurement category III
Maximum altitude 1000m without derating (above 1000m, apply a derating
of the starter current by 0.5%/100m)
Climate sequence Z/ABDM (IEC/EN 60068-2-61)
Shock resistance 15g (IEC/EN 60068-2-27)
10g if used with accessory EXP8003
Vibration resistance 0.7g (IEC/EN 60068-2-6)
Supply - relay connections
Terminal types Screw-type (fixed)
Wire cross-section (min and max) 0.2...4mm
2
(26...10 AWG)
Tightening torque 0.8 Nm (7 lbin)
Type of conductor Use copper conductors only, 75°C
Fan supply and digital inputs connections
Terminal types Screw-type (fixed)
Wire cross-section (min and max) 0.2 - 2.5mm
2
(24 - 12 AWG)
Tightening torque 0.44 Nm (4 lbin)
Type of conductor Use copper conductors only, 75°C
Power connections for ADXL from 18 to 115A
Terminal types Fixed, double
Wire cross-section (min and max) 2 x 2,5-35mm
2
2 x 18-2 AWG
Tightening torque for 4-5 Nm / 2.95-3.69 lbft
ADXL 0018 600 … ADXL 0060 600
Tightening torque for 5.5-6.5 Nm / 4.06-4.79 Ibft
ADXL 0075 600 … ADXL 0115 600
Type of conductor Use copper conductors only, 75°C
Power connections for ADXL from 135 to 320A
Type of bars 25x5mm, hole diam.11mm
Type of conductor Use copper conductors only, 75°C
Conductors section for ADXL 0135 600 Max. 50 mm
2
1 x AWG 3/0 (use n° 2 lugs kit code EXA 01 +
n° 2 terminal shrouds kit code EXA 02)
Conductors section for ADXL 0162 600 Max. 70 mm
2
1 x AWG 3/0 (use n° 2 lugs kit code EXA 01 +
n° 2 terminal shrouds kit code EXA 02)
Conductors section for ADXL 0195 600 Max. 95 mm
2
1 x AWG 3/0 (use n° 2 lugs kit code EXA 01 +
n° 2 terminal shrouds kit code EXA 02)
Conductors section for ADXL 0250 600 Max. 120 mm
2
2 x AWG 3/0 (use n° 2 lugs kit code EXA 03 +
n° 2 terminal shrouds kit code EXA 04)
Conductors section for ADXL 0320 600 Max. 185 mm
2
2 x AWG 3/0 (use n° 2 lugs kit code EXA 03 +
n° 2 terminal shrouds kit code EXA 04)
Type of wrench Socket wrench 17mm
Tightening torque for 35 Nm / 310 in-lbs
ADXL 0135 600 … ADXL 0320 600
Tightening torque for lugs EXA... 42 Nm / 375 in-lbs
Container
Execution Panel interior
Material Polycarbonate RAL 7035
Protection rating IP00
Mounting Screw or DIN-rail (IEC/EN60715) via optional accessory
EXP8003 (only for ADXL0030600 ... ADXL0115600)
Weight
ADXL 0018 600, ADXL 0030 600 1970g
ADXL 0045 600, ADXL 0060 600 1970g
ADXL 0075 600, ADXL 0085 600, ADXL 0115 600 2704g
ADXL 0135 600, ADXL 0162 600 7350g
ADXL 0195 600, ADXL 0250 600, ADXL 0320 600 12730g
Type-approvals and conformity
Type-approvals obtained cULus for all sizes.
EAC and RCM for ADXL 0030 600 … ADXL 0320 600
Type-approvals pending EAC and RCM for ADXL 0018 600
Conformity to standards IEC/EN 60947-4-2:2011, IEC/EN 60947-1:2014,
IEC/EN 60068-2-61, IEC/EN 60068-2-27,
IEC/EN 60068-2-6, UL508, CSA C22.2-N°14
TECHNICAL CHARACTERISTICS
Auxiliary supply: terminals A1-A2
Us rated voltage 100 - 240V
Operating range 90 - 264V
Frequency 45 - 66Hz
Power draw/dissipation Size 1 100V
110mA 5.5W
240V
70mA 5.8W
Size 2 100V
120mA 6.8W
240V
75mA 7W
Size 3 100V
125mA 7W
240V
75mA 7,2W
Size 4 100V
125mA 7W
240V
75mA 7,2W
Immunity time for micro-interruptions
40ms (110V
)
160ms (220V
)
Motor supply voltage L1 – L2 – L3
Operating range 208-600V
±10%
Frequency range 50/60Hz (limits: at 50Hz: 47.5-52.5Hz,
at 60Hz: 56.4-63.6Hz)
Rated current and power (see table “Choosing the soft starter”, page 22)
Digital inputs, terminals C - IN1, IN2
Input type Negative
Applied voltage at contact 5V=
Input current
10mA
Low input signal
0,8V
High input signal
3,2V
Input signal delay
50ms
PTC input, terminals C - IN3
Compatible types of PTC sensor 2 wires, conforming with DIN 44081
Total PTC sensor resistance
1,5k
at 25°C
Trip resistance
≅
2,9k
Reset resistance
≅
1,6k
Fan power, terminals FAN + / -
Fan voltage 5V= supplied by soft starter
(only for ADXL 0018 600..ADXL 0115 600)
Fan type Use exclusively accessory code EXP8004
Output, terminals 11-12-14
Output arrangement: 1 NO/NC switching contact
Operating voltage 250V
Ratings NO contact AC1 5A-250V
5A 30V=
NC contact AC1 3A-250V
3A 30V=
UL ratings D300
Maximum switching voltage 250V
Electrical duration NC contact – 10x10
3
cycles
NO contact – 20x10
3
cycles
Mechanical duration 10
7
cycles
Output, terminals 21-24, 34
Output arrangement 2 x 1 NO
Operating voltage 250V
Nominal thermal rating 3A 250V
3A 30V=
UL ratings 3A 30V= L/R 0ms - 3A 250V~ cos
1
Maximum switching voltage 250V
Electrical/mechanical duration 2 x 10
7
/ 1 x 10
5
Insulation voltage
Rated insulation voltage Ui 600V
Rated impulse withstand voltage Uimp 9.5kV
Operating frequency withstand voltage 5.2kV
Ambient operating conditions
Operating temperature -20...+40°C
(max temperature 60°C, from 40° to 60°C apply a
derating of the starter current by 0.5%/°C)
Storage temperature -30...+80°C
Relative humidity <80% (IEC/EN 60068-2-78)
GB
MANUAL REVIEW HISTORY
Rev Date Notes
00 29/06/2016 – First release
01 03/10/2016 – Second release
02 24/02/2017 – Third release
03 26/04/2017 – Fourth release
04 26/07/2017 – Fifth release