CX02 DONGLE USAGE
– The CX02 dongle offers WiFi Access point capability for connection to PC, tablet or smartphones. In addition to this function it also offer the possibility to store and transfer a block of data from/to the DCRL8
– Insert the interface CX02 into the IR port of DCRL8 on the front plate
– Switch CX02 on by pressing the button for 2 sec
– Wait until the LINK LED becomes orange flashing
– Press 3 times consecutively and fast the dongle button
– At this point the display of the DCRL8 shows the first of the 6 possible commands (D1…D6)
– Press
to select the desired command
– Press AUT to execute the selected command. The unit will prompt for a confirmation (OK?). Press once again AUT to confirm or MODE to cancel
– The following table lists the possible commands:
– For additional details see CX02 operating manual.
INSTALLATION
– DCRL8 is designed for flush-mount installation. With proper mounting and using dedicated gasket, it guarantees IP65 front protection
– From inside the panel, for each four of the fixing clips, position the clip in one of the two sliding guide, then press on the clip corner until the second guide snaps in
– From inside the panel, for each four of the fixing clips, position the clip in its square hole on the housing side,then move it backwards in order to position the hook
– Repeat the same operation for the four clips
– Tighten the fixing screw with a maximum torque of 0.5Nm
– In case it is necessary to dismount the device, repeat the steps in opposite order.
– For the electrical connections, see the wiring diagrams in the dedicated chapter and the requirements reported in the technical characteristics.
CODE
COMMAND
DESCRIPTION
D1
SETUP DEVICE
CX02
Copies Setup settings from DCRL8 to CX02.
D2
SETUP CX02
DEVICE
Copies Setup settings from CX02 to DCRL8.
D3
CLONE DEVICE
CX02
Copies Setup settings and working data from DCRL8 to CX02.
D4
CLONE CX02
DEVICE
Copies Setup settings and working data from CX02 to DCRL8.
D5
INFO DATA CX02
Shows information about data stored into CX02.
D6
EXIT
Exits from dongle menu.
WIRING DIAGRAMS
WARNING!
Disconnect the line and the supply when servicing on terminals.
Three-phase standard wiring
THREE-PHASE STANDARD CONNECTION (default)
Default wiring configuration for standard applications.
Voltage measure 1 ph-to-ph voltage reading L1-L2
Current measure L3 phase
Phase angle offset Between V (L1-L2 ) and I (L3)
90°
Capacitor overload current measure 1 reading calculated on L1-L2
Parameter setting P.03 = L3
P.05 = L1-L2
P.24 = 3PH
L1 L2 L3
MAINS
LOAD
QS1
CT1
DCRL 8
1 2
3 4
5
1
2
5
6
7
8
9 10 11 12
FU10
2x1A
FU11
2x1A
14
13
4
FU9
R
INPUT
CURRENT
S1 S2
INPUT
VOLTAGE
100-600V
AUX
SUPPLY
100-440V
6
7
8
15
16 17 18
FU9
10A
FU10
5A
FU1
KM1
KM2
R
FU2
R
R
R
R
FU8
K8
TC1
K1
K2
K8
NOTES
– The polarity of the current/voltage input is irrelevant.
– For three-phase connection, the voltage input must be connected phase to phase; the current transformer must be connected on the remaining phase.
BFK contactors