P05.01, P05.02, P05.03 

– The first two parameters define the minimum voltage threshold and the

related hysteresis upon restore. P05.02 cannot be set to a lower value than P05.01. P05.03 defines the

intervention delay of this protection; if set to POT the value is set via the LINE 1 potentiometer

(adjustable between 0 and 60 seconds).

P05.04, P05.05, P05.06

– The first two parameters define the maximum voltage threshold and the

related hysteresis upon restore. P05.05 cannot be set to a value exceeding P05.04. Setting P05.04 to OFF

will disable the maximum voltage control. P05.06 defines the maximum voltage intervention delay; if set

to POT the value is set via the LINE 1 potentiometer (adjustable between 0 and 60 seconds).

P05.07

– Delay for LINE 1 restore to the limit range, used when the LINE 2 source is not available.

Generally shorter than P05.08, as there is the urgent need to supply power because the load is not

energized. If set to POT the value is set via the LINE 1 potentiometer (adjustable between 0 and 60

seconds).

P05.08

– Delay for LINE 1 restore to the limit range, used when the load can be connected to LINE 2.

Generally longer than P05.07, as the load is energized and consequently it is possible to wait longer

before considering voltage steadily restored. If set to POT the value is set via the LINE 1 potentiometer

(adjustable between 0 and 60 seconds).

P05.09, P05.10

– Voltage threshold below which a phase loss intervention occurs, generally quicker

than the drop. The delay for the phase loss is specified by P05.10; if set to POT the value is set via the

LINE 1 potentiometer (adjustable between 0 and 60 seconds).

P05.11, P05.12

– P05.11 defines the maximum threshold for unbalance between phases, referred to

voltage rating, and P05.12 defines the related intervention delay; if set to POT the value is set via the

LINE 1 potentiometer (adjustable between 0 and 60 seconds). This control may be disabled by setting

P05.11 to OFF.

P05.13

– Max. frequency intervention threshold (can be disabled).

P05.14

– Max. frequency intervention delay. If set to POT the value is set via the LINE 1 potentiometer

(adjustable between 0 and 60 seconds).

P05.15

– Min. frequency intervention threshold (can be disabled).

P05.16

– Min. frequency intervention delay. If set to POT the value is set via the LINE 1 potentiometer

(adjustable between 0 and 60 seconds).

P05.01, P05.02, P05.03

– Los dos primeros parámetros definen el umbral de tensión mínima y la

correspondiente histéresis durante el restablecimiento. P05.02 no se puede configurar en un valor
inferior al del parámetro P05.01. P05.03 define el tiempo de retardo para la intervención de esta
protección; si se ajusta en POT, el valor se configura mediante el potenciómetro LINE 1 (entre 0 y 60
segundos). 

P05.04, P05.05, P05.06

– Los dos primeros parámetros definen el umbral de tensión máxima y la

correspondiente histéresis durante el restablecimiento. P05.05 no se puede configurar en un valor
superior al del parámetro P05.04. El control de tensión máxima se desactiva cuando P05.04 se configura
en OFF. P05.06 define el retardo de intervención de tensión máxima; si se ajusta en POT, el valor se
configura mediante el potenciómetro LINE 1 (entre 0 y 60 segundos).

P05.07

– Tiempo de restablecimiento de la LÍNEA 1 dentro de los límites; se utiliza cuando la fuente de la

LÍNEA 2 no está disponible. Normalmente es menor que el valor establecido en P05.08 dada la urgencia
de suministrar tensión ante la ausencia del suministro de carga. Si se ajusta en POT, el valor se configura
mediante el potenciómetro LINE 1 (entre 0 y 60 segundos).

P05.08

– Tiempo de retardo de restablecimiento de la LÍNEA 1 dentro de los límites; se utiliza cuando la

carga puede conectarse a la LÍNEA 2. Suele ser un tiempo superior al del parámetro P05.07 porque el
suministro de carga permite esperar más antes de considerar que la tensión se ha restablecido y está
estable. Si se ajusta en POT, el valor se configura mediante el potenciómetro LINE 1 (entre 0 y 60
segundos).

P05.09, P05.10

– Umbral de tensión por debajo del cual se produce una intervención por pérdida de

fase, por lo general con más rapidez que la caída. El tiempo de retardo para la pérdida de fase se
especifica en P05.10; si se ajusta en POT, el valor se configura mediante el potenciómetro LINE 1 (entre
0 y 60 segundos).

P05.11, P05.12

– P05.11 define el umbral máximo de desequilibrio entre fases con respecto a la tensión

nominal y P05.12 define el retardo de intervención correspondiente; si se ajusta en POT, el valor se
configura mediante el potenciómetro LINE 1 (entre 0 y 60 segundos). Este control se puede desactivar si
se configura P05.11 en OFF.

P05.13

– Umbral de intervención de frecuencia máxima; se puede desactivar.

P05.14

– Retardo de intervención de frecuencia máxima. Si se ajusta en POT, el valor se configura

mediante el potenciómetro LINE 1 (entre 0 y 60 segundos).

P05.15

– Umbral de intervención de frecuencia mínima; se puede desactivar.

P05.16

– Retardo de intervención de frecuencia mínima. Si se ajusta en POT, el valor se configura

mediante el potenciómetro LINE 1 (entre 0 y 60 segundos).

Note: for details on the functions of parameters see the menu 

M05 – LINE 1 control.

Nota: consulte la explicación de la función de los parámetros en el menú 

M05 – Control de LÍNEA 1.

 M05 - LINE 1 CONTROL / CONTROL DE LÍNEA 1                                                                                                                                                                           UoM                 Default/por defecto          Range/Rango

 P05.01       MIN voltage limit / Límite de tensión MÍN.                                                                                                                                                                      %                                85                            70-100

 P05.02       MIN voltage pick-up / Umbral MÍN. restablecimiento                                                                                                                                                      %                                90                            70-100

 P05.03       MIN voltage delay / Retardo de tensión MÍN.                                                                                                                                                                   s                                  5                           POT/0-600

 P05.04       MAX voltage limit / Límite de tensión MÁX.                                                                                                                                                                    %                               115                      100-130 / OFF

 P05.05       MAX voltage pick-up / Umbral MÁX. restablecimiento                                                                                                                                                    %                               110                      100-130 / OFF

 P05.06       MAX voltage delay / Retardo de tensión MÁX.                                                                                                                                                                 s                                  5                           POT/0-600

 P05.07       Presence delay (when LINE 2 source not available) /                                                                                                                                                       s                                POT                       POT/1-6000

                   Retardo de tensión (retardo de restablecimiento de red dentro de los límites con LÍNEA 2 no disponible)

 P05.08       Presence delay like 2 ok (when LINE 2 source available)                                                                                                                                                 s                                POT                       POT/1-6000

                   Retardo de tensión de LÍNEA 2 correcto (retardo de restablecimiento de red dentro de los límites con LÍNEA 2 disponible)

 P05.09       Phase failure threshold / Umbral de pérdida de fase                                                                                                                                                       %                                70                          60-80/OFF

 P05.10       Phase failure delay / Retardo de pérdida de fase                                                                                                                                                              s                                 0.1                       POT/0.1-30.0

 P05.11       MAX asymmetry limit / Umbral de asimetría MÁX.                                                                                                                                                         %                                15                           1-20/OFF

 P05.12       MAX asymmetry delay / Retardo de asimetría MÁX.                                                                                                                                                        s                                 5.0                      POT/0.1-900.0

 P05.13       MAX frequency limit / Límite de frecuencia MÁX.                                                                                                                                                           %                               105                       100-120/OFF

 P05.14       MAX frequency delay / Retardo de frecuencia MÁX.                                                                                                                                                        s                                  3                           POT/0-600

 P05.15       MIN frequency limit / Límite de frecuencia MÍN.                                                                                                                                                             %                                95                         OFF/80-100

 P05.16       MIN frequency delay / Retardo de frecuencia MÍN.                                                                                                                                                          s                                  5                           POT/0-600

 M06 - LINE 2 CONTROL / CONTROL DE LÍNEA 2                                                                                                                                                                           UoM                 Default/por defecto          Range/Rango

 P06.01       MIN voltage limit / Límite de tensión MÍN.                                                                                                                                                                      %                                85                            70-100

 P06.02       MIN voltage pick-up / Umbral MÍN. restablecimiento                                                                                                                                                      %                                90                            70-100

 P06.03       MIN voltage delay / Retardo de tensión MÍN.                                                                                                                                                                   s                                  5                           POT/0-600

 P06.04       MAX voltage limit / Límite de tensión MÁX.                                                                                                                                                                    %                               115                      100-130 / OFF

 P06.05       MAX voltage pick-up / Umbral MÁX. restablecimiento                                                                                                                                                    %                               110                      100-130 / OFF

 P06.06       MAX voltage delay / Retardo de tensión MÁX.                                                                                                                                                                 s                                  5                           POT/0-600

 P06.07       Presence delay (when LINE 1source not available)                                                                                                                                                          s                                POT                       POT/1-6000

                   Retardo de tensión (retardo de restablecimiento de red dentro de los límites con LÍNEA 1 no disponible) 

 P06.08       Presence delay LINE 1 ok (when LINE 1 source available)                                                                                                                                               s                                POT                       POT/1-6000

                   Retardo de tensión de LÍNEA 1 correcto (retardo de restablecimiento de red dentro de los límites con LÍNEA 1 disponible)

 P06.09       Phase failure threshold / Umbral de pérdida de fase                                                                                                                                                       %                                70                          60-80/OFF

 P06.10       Phase failure delay / Retardo de pérdida de fase                                                                                                                                                              s                                 0.1                       POT/0.1-30.0

 P06.11       MAX asymmetry limit / Umbral de asimetría MÁX.                                                                                                                                                         %                                15                           1-20/OFF

 P06.12       MAX asymmetry delay / Retardo de asimetría MÁX.                                                                                                                                                        s                                 5.0                      POT/0.1-900.0

 P06.13       MAX frequency limit / Límite de frecuencia MÁX.                                                                                                                                                           %                               105                       100-120/OFF

 P06.14       MAX frequency delay / Retardo de frecuencia MÁX.                                                                                                                                                        s                                  3                           POT/0-600

 P06.15       MIN frequency limit / Límite de frecuencia MÍN.                                                                                                                                                             %                                95                         OFF/80-100

 P06.16       MIN frequency delay / Retardo de frecuencia MÍN.                                                                                                                                                          s                                  5                           POT/0-600

Содержание ATL500

Страница 1: ...onal und unter Befolgung der einschl gigen Vorschriften installiert werden Vor jedem Eingriff am Instrument die Spannungszufuhr zu den Messeing ngen trennen und die Stromwandler kurzschlie en Bei zwec...

Страница 2: ...tales 3 Modos de funcionamiento 3 Puesta en marcha 3 Entradas y salidas programables 4 Bloqueo del teclado 4 Funciones de los potenci metros 4 Configuraci n de par metros mediante un smartphone o una...

Страница 3: ...ndo el bot n correspondiente a la l nea a la que se quiere conectar la carga se puede elegir entre I L NEA 1 0 posici n neutra carga desconectada o II L NEA 2 En el caso de las aplicaciones de red y g...

Страница 4: ...art device it appears automatically a link to Google Play Store for the download of the App 4 Install the LOVATO NFC App on the smart device 5 Open the LOVATO NFC App and click on the button Download...

Страница 5: ...programables M09 VARIOS Configuraci n del retardo de arranque del generador tras el fallo de la l nea y tiempo de refrigeraci n del generador M10 TABLA DE ALARMAS Activaci n y propiedades de alarma In...

Страница 6: ...le closing command active in addition to the generation of the proper switch failure alarm A01 or A02 the load is switched to the alternative source P04 01 Define la l nea principal es decir la que as...

Страница 7: ...el valor se configura mediante el potenci metro LINE 1 entre 0 y 60 segundos P05 09 P05 10 Umbral de tensi n por debajo del cual se produce una intervenci n por p rdida de fase por lo general con m s...

Страница 8: ...larm 3 flashes A03 alarm etc The meaning of the alarm is described in the Alarms table Alarms can be reset by pressing the MAN key Note After pressing MAN key the ATL 500 goes in manual operative mode...

Страница 9: ...informaci n Funci n Descripci n Desactivado Entrada desactivada Realimentaci n de L NEA 1 Contacto auxiliar que indica a la unidad ATL 500 si el dispositivo de conmutaci n de la L NEA 1 est abierto o...

Страница 10: ...e activa cuando se satisfacen todas las condiciones para conectar la carga a la L NEA 2 Modo MAN Salida que se activa cuando el conmutador ATL 500 est en modo manual Modo AUT Salida que se activa cuan...

Страница 11: ...exi n bif sica WIRING DIAGRAMS Control of contactors three phase connection ESQUEMAS DE CONEXI N Control de contactores conexi n trif sica Parameter setting for the wiring diagram in picture Programac...

Страница 12: ...1 2 open Apertura de L NEA 1 y L NEA 2 Control of motorized changeover switch Control de conmutador motorizado Dual power supply implementation with auxiliary voltage control for motorized changeover...

Страница 13: ...UT1 OUT3 B300 250V 8A AC1 1A 30V PILOT DUTY INP 1 INP 2 COM OUT 3 OUT 1 OUT 2 5 6 7 8 1 2 3 4 L1 L2 L3 N L1 L2 L3 N LINE 1 110 240V LN 190 415V 3N 50 60Hz LINE 2 110 240V LN 190 415V 3N 50 60Hz MECHAN...

Страница 14: ...i n de tensi n de L NEA 1 y L NEA 2 terminales 1 4 y 5 8 Tensi n nominal 110 a 240V LN 190 a 415V 3N L mites de funcionamiento con tensi n 90 a 300V LN 155 a 519V 3N Frecuencia nominal 50 60Hz Gama de...

Отзывы: