1) Introduction 

To meet its policy concerning EMC, based on the Community directives 

2014/30/EU 

2014/35/EU

, the 

LOREME company takes into account the standards relative to this directives from the very start of the con-
ception of each product. 
The set of tests performed on the devices, designed to work in an industrial environment, are made in accor-
dance with 

IEC 61000-6-4 

and 

IEC 61000-6-2 

standards in order to establish the EU declaration of confor-

mity. The devices being in certain typical configurations during the tests, it is impossible to guarantee the re-
sults in every possible configurations. To ensure optimum operation of each device, it would be judicious to 
comply with several recommendations of use. 

 
2) Recommendations of use 
2.1 ) General remarks 

- Comply with the recommendations of assembly indicated in the technical sheet (direction of assembly, 
spacing between the devices, ...). 
- Comply with the recommendations of use indicated in the technical sheet (temperature range, protection 
index). 
- Avoid dust and excessive humidity, corrosive gas, considerable sources of heat. 
- Avoid disturbed environments and disruptive phenomena or elements. 
- If possible, group together the instrumentation devices in a zone separated from the power and relay cir-
cuits. 
- Avoid the direct proximity with considerable power distance switches, contactors, relays, thyristor power 
groups, ... 
- Do not get closer within fifty centimeters of a device with a transmitter (walkie-talkie) of a power of 5 W, be-
cause the latter can create a field with an intensity higher than 10 V/M for a distance fewer than 50 cm. 

 
2.2 ) Power supply 

- Comply with the features indicated in the technical sheet (power supply voltage, frequency, allowance of the 
values, stability, variations ...). 
- It is better that the power supply should come from a system with section switches equipped with fuses for 
the instrumentation element and that the power supply line be the most direct possible from the section 
switch. 
- Avoid using this power supply for the control of relays, of contactors, of electrogates,  ... 
- If the switching of thyristor statical groups, of engines, of speed variator, ... causes strong interferences on 
the power supply circuit, it would be necessary to put an insulation transformer especially intended for instru-
mentation linking the screen to earth. 
- It is also important that the installation should have a good earth system and it is better that the voltage in 
relation to the neutral should not exceed 1V, and the resistance be inferior to 6 ohms. 
- If the installation is near high frequency generators or installations of arc welding, it is better to put suitable 
section filters. 
 

2.3 ) Inputs / Outputs 

- In harsh conditions, it is advisable to use sheathed and twisted cables whose ground braid will be linked to 
the earth at a single point. 
- It is advisable to separate the input / output lines from the power supply lines in order to avoid the coupling 
phenomena. 
- It is also advisable to limit the lengths of data cables as much as possible. 

 

 
EMC Consideration 

Содержание THL105

Страница 1: ...S AND RIBBONS LOREME 12 rue des Potiers d Etain Actipole BORNY B P 35014 57071 METZ CEDEX 3 Phone 03 87 76 32 51 Contact Commercial Loreme fr Technique Loreme fr Download manual at www loreme fr CONFI...

Страница 2: ...RATION p3 1 Hysteresis configuration p4 2 Delay configuration p4 3 End of configuration p4 RS232 LINK SETTING p5 TERMINAL MODE p6 Visualization p6 Configuration p6 1 Method p6 2 Configurable parameter...

Страница 3: ...etpoint The button allows you to increment the setpoint and the button to decrement it The setpoint is incremented or decremented in steps of 1 C at the beginning Holding pressed the or button for mor...

Страница 4: ...e Config button to validate the setting 0 to 50 C 2 Delay configuration RETARD Press the or button to increment or decrement the delay value 0 1 s steps 0s Press the Config button to validate the sett...

Страница 5: ...ates another communication port number COMx and re quires the reconfiguration of the HyperTerminal The terminal emulation software for PC HyperTerminal is resident in windows up to XP version For late...

Страница 6: ...modification by typing Enter The modification with simultaneous display followed by validation with Enter key 2 Configurable parameters The following parameters can be configured The threshold setpoin...

Страница 7: ...s 100 5 C Temperature value with offset OFFSET 0 5 offset function temperature offset value Use keys and to adjust offset the temperature is directly modified Type on Enter to save the new offset OFFS...

Страница 8: ...waiting mode This file is provide by LOREME This file contain the firmware code in intel HEX format Selected the Transfer Send a text file in the HyperTerminal menu Select the directory and open the...

Страница 9: ...n fifty centimeters of a device with a transmitter walkie talkie of a power of 5 W be cause the latter can create a field with an intensity higher than 10 V M for a distance fewer than 50 cm 2 2 Power...

Страница 10: ...Loreme fr Technique Loreme fr Wirings PC DEVICE LINK DIAGRAMS OF CONNECTIONS 3 terminals plug to THL105 LINK in FRONT FACE under the cover Female 9 terminals to PC 3 5 2 Cover lift here PT100 sensor P...

Отзывы: