A temporary message appears at the beginning, indicating the version of the device (Rev Hard.Soft).
CONFIGURATION
Rev:0.1
1) Hysteresis (dead band) configuration
HYSTERESIS?
Press the
or
button to increment or decrement the hysteresis value (1 °C steps).
2°C
Press the '
Config
' button to validate the setting (0 to 50 °C).
2) Delay configuration
RETARD?
Press the
or
button to increment or decrement the delay value (0.1 s steps).
0s
Press the '
Config
' button to validate the setting (0 to 300 s).
3) End of configuration
The new parameters are saved in non volatile memory and the message
‘
OK
’
is displayed briefly, indicating that the
parameters have been successfully saved. Then, device returns to measure mode.
Note:
If the waiting time for action on the buttons exceeds 90 seconds then the device automatically returns to measurement
mode without saving the new settings.