Filter  Jump  value

See the Easy/Advanced mode selection page near the beginning of this manual, and
choose advanced mode.

The Filter Jump value allows you to decide how the display will respond to a process step
change. It does this by overriding the filtering, if the input signal moves by more than a
chosen amount in one conversion. The Filter Jump default value is 10%.

This means that for noise amplitude which has a peak value of less than 10% of the input
range, filtering will be applied. Any signal movement greater than 10% of the input range will
cause the display to jump immediately to that value, without filtering.  After that jump, normal
filtering will be re-applied, provided signal movement thereafter  is less than 10% per con-
version.

Guidance:

For  noisy systems, increase the Filter Jump value up to a maximum of  99. Choose a value
which gives a good compromise between filtering and response speed.

For reasonably clean signals, a Filter Jump value of around 10 or less will give a good
compromise between filtering and response speed to step change inputs.

Set1

Set2

Output

Alarms

Digit

OK

Max/Min

Reset

Lockout Switch must be OFF

Press 3 seconds

Set1

Set2

Output

Alarms

Digit

OK

Max/Min

Reset

Set1

Set2

Output

Alarms

Digit

OK

Max/Min

Reset

Set1

Set2

Output

Alarms

Digit

OK

Max/Min

Reset

Press repeatedly to accept and return to display

Done!

Press repeatedly until you see

FiL.J.

XX

  where 

XX

 is the Filter

Jump percentage

(Default = 

FiL.J.09

)

You can set from

  00

 to 

99

. Use the

DIGIT and  UP or DOWN button to
increase or decrease this value.

1

2

3

4

OFF

Circuit board        ON

Содержание INTUITIVE INT4-P

Страница 1: ...whole manual before you install this meter London Electronics Limited Thorncote Road NearSandy Bedfordshire SG19 1PU Tel 44 0 1767 626444 Fax 44 0 1767 626446 www london electronics com help london el...

Страница 2: ...de the environmental specification of the product 4 Mishandling or abuse The warranty set forth above is exclusive and no other warranty whether written or oral is expressed or implied We specifically...

Страница 3: ...7 Logic Input connections Front Buttons 28 Factory defaults 29 CalibrationAudit number 29 Signal Filtering Averaging 30 31 Last Digit rounding 32 Scale Factor adjustment 33 OffsetAdjustment 34 Menu Ti...

Страница 4: ...rs fromelectric shock We designed this meter for Pollution Degree 2 environments only Power supplies to this equipment must have anti surge T fuses rated at 400mA for 230V supply 400mA for 110V supply...

Страница 5: ...hutdown periods you may have to to wait several weeks for an equivalent replacement or we may have no stock at the time you urgently need it You mayalso needto pay extra carriagecharges ifyou wanta fa...

Страница 6: ...240 VAC or 11 30VDC These meters are designed to mount into a protective enclosure which will protect users from contact with power and signal wiring Theseunits mustbe installedfully assembled and mus...

Страница 7: ...of meter U Bracket Bracket screw 1 of 2 Left side of meter case U Bracket Bracket screws U Bracket Bracket screws Slide the meter with gasket into the panel cutout Securing into the panel Re fit the...

Страница 8: ...using the 4 buttons Output functions include isolated 16 bit 4 20mA 0 10V 10 to 10V RS232 RS485 and up to 4 alarms with a wide choice of alarm functions Install the meters in a suitable protective ele...

Страница 9: ...sealed IP65 all round and is supplied with the meter in stalled for you to wire to via 3 cable glands It comes complete with SPC4 splashproof cover We also offer a dual version of this enclosure which...

Страница 10: ...5mm2 Tighten screw terminals to 7 0 lb in torque 0 8 Nm torque Cable insulation voltage rating Cables shall have an insulation voltage rating of at least 380V continuous Wire preparation We recommend...

Страница 11: ...installed Refertoratinglabel toseeinstalledoptions Class II Installation Not used Fuse Switch Circuit breaker Power Customer supplied disconnection and overload protection devices 1 2 3 4 5 6 7 8 9 10...

Страница 12: ...cancelled Mixing destinations carelessly amongst the twisted pairs can actually worsen noise performance 3 The cable should be routed away from noisy wiring and devices such as power feeds frominverte...

Страница 13: ...several displays to several sensors please be sure to use one twisted pair for each display and sensor Do NOT use a wire from one pair for signal positive and a wire from another pair for signal nega...

Страница 14: ...14 Application Notes...

Страница 15: ...nch menu prompts Lockout Switch must be OFF Press together briefly Set1 Set2 Output Alarms Digit OK Max Min Reset Display shows UI Eng Default for User Interface English or UI FrA for User Interface F...

Страница 16: ...isplay shows bright Each press of the UP button will select a newbrightness level There are 7 brightness levels to choose from Default Full brightness Set1 Set2 Output Alarms Digit OK Max Min Reset Pr...

Страница 17: ...play should show for each signal level How to choose a calibration method Lockout Switch must be OFF Press 3 seconds Set1 Set2 Output Alarms Digit OK Max Min Reset Press to select dirECt or thEor Disp...

Страница 18: ...y SEt Hi Press 3 seconds Set1 Set2 Output Alarms Digit OK Max Min Reset Apply the highest calibration signal you can achieve ideally 100 of system capacity You can use less but you will get better acc...

Страница 19: ...to protect your settings OK Max Min Reset Lockout Switch must be OFF Set1 Set2 Output Alarms Digit OK Max Min Reset Apply the lowest calibration signal you can achieve ideally 0 of system capacity Pr...

Страница 20: ...y so that the display shows Lin On then press OK Set1 Set2 Output Alarms Digit OK Max Min Reset 1 2 3 Set1 Set2 Output Alarms Digit OK Max Min Reset The display will show SEt 00 Ensure no load is appl...

Страница 21: ...y will show Add Pt Press OK if you want toAdd another calibration point you will repeat the previ ous steps each time incrementing Set 02 and rd 02 up to Set 09 and rd 09 which are the last available...

Страница 22: ...0000 if your input is 4 20mA Set1 Set2 Output Alarms Digit OK Max Min Reset Press to accept Set1 Set2 Output Alarms Digit OK Max Min Reset Display now shows rd Hi briefly You can now specify the maxi...

Страница 23: ...t each digit in turn and the UP or DOWN arrow to increase or decrease each digit s value as re quired eg set 000 000 if your display range is 0 to 100 000 Theoretical Calibration Low end calibration T...

Страница 24: ...show In 00 followed by an editing screen Here you can enter your first calibration input signal level using DIGIT button to select each digit in turn Increase or decrease the value of each digit using...

Страница 25: ...utton and increase or decrease each digit s value using the UP or DOWN button until the display is set as required Press OK when done The display will show Add Pt Press OK if you want toAdd another ca...

Страница 26: ...d is only applied for readings less than 8 least significant counts The corrected value is stored in non volatile memory so that any drift trend will be re ap plied after you have switched off the met...

Страница 27: ...owed by the existing function for Contact Closure 1 After you have set CC 1 you will get the prompt CC 2 to allow you to set Contact Closure 2 function and when you have set CC 2 you will get the prom...

Страница 28: ...eset buttons also Or simply link NPN could be opto isolators if you need the logic control lines to be galvanically isolated from the input signal ON OFF Set1 Set2 Output Alarms Digit OK Max Min Reset...

Страница 29: ...set Press to accept 1 2 3 Done Display shows defs n Defaults no Press the DOWN button to change the display to defs y Defaults Yes if you want to return to default conditions Press together for 3 seco...

Страница 30: ...shows FIL XX X where XX X is the time constant in seconds Use the UP or DOWN button to increase or decrease this value Default FIl 00 0 Set1 Set2 Output Alarms Digit OK Max Min Reset Press to accept 1...

Страница 31: ...gnal movement thereafter is less than 10 per con version Guidance For noisy systems increase the Filter Jump value up to a maximumof 99 Choose a value which gives a good compromise between filtering a...

Страница 32: ...display can be set to round up to the nearest 1 no rounding 2 5 10 20 or 50 Lockout Switch must be OFF Press 3 seconds Set1 Set2 Output Alarms Digit OK Max Min Reset Press repeatedly until you see LS...

Страница 33: ...hange of 1 8 Degrees F A scale factor of 1 8 So we set Scale 1 8 and offset 32 See next page for offset setting 3 Changing from Degrees F to Degrees C 0 Degrees F is 17 8 degrees C A 17 8 degree C off...

Страница 34: ...n with the SCALE feature on the previous page Lockout Switch must be OFF Press 3 seconds Set1 Set2 Output Alarms Digit OK Max Min Reset Press repeatedly until you see OFFSEt followed by the existing o...

Страница 35: ...Lockout Switch must be OFF Press together briefly Set1 Set2 Output Alarms Digit OK Max Min Reset Press repeatedly until you see dLAY XX where XX is the delay in seconds Choices are dLAy 1 0 dLAy 20 d...

Страница 36: ...er briefly Set1 Set2 Output Alarms Digit OK Max Min Reset Press OK button briefly and repeatedly until you see rEV d 0 Default or rEV d 1 Set1 Set2 Output Alarms Digit OK Max Min Reset Press briefly t...

Страница 37: ...git OK Max Min Reset Press OK button briefly and repeatedly until you see boot 0 or boot 1 or boot 2 or boot 3 displayed Set1 Set2 Output Alarms Digit OK Max Min Reset Press briefly to toggle 1 2 3 4...

Страница 38: ...n 4 Press the Up arrow to change display to defs Y and press OK 5 If you want all channels to share a common setting eg calibration do that setting now 6 When you want to do separate settings for each...

Страница 39: ...re than this the resistor has probably been overloaded and burned by having a voltage connected across it Please check your field wiring to en sure that no more than 30mA or 1V can be applied to the c...

Страница 40: ...n in the diagram If the meter doesn t yet have an output option board the top screw may not yet be fitted 4 Slide the electronic boards out throught the front of the case You can easily separate the u...

Страница 41: ...o dispose of it It must not be thrown away with general rubbish If you are unable to dispose of this item locally you may send it to us for recycling Conditions 1 We will only accept items of our manu...

Страница 42: ...bipolar 0 10V 0 5V 1 5V 0 10mA 0 20mA 4 20mA Input Resistance 1 Megohm for voltage 2 Ohms for current inputs Accuracy 0 05 of range Allow 30 minutes after switch on for thermal stabilisation Span temp...

Страница 43: ...ncludes relay output wiring All signal cabling shall be screened The screen shall only be terminated to the power earth terminal at the meter end of the cable Declared as true and correct for and on b...

Страница 44: ...itoring and control equipment All our UK manufactured products have a 3 year warranty Real Time Production Line Displays Digital Panel Meters Message Displays sealed IP65 Large Digital Displays sealed...

Отзывы: