22
Max/Min
Reset
Theoretical Cal. - Decimal Point & Full Scale
This is when you type in the sensor’s theoretical signal level at the top and bottom of
its range and the value to display, for each signal level.
If you have not done so before, please select Theoretical Calibration
mode from the
Meter Calibration
page AND choose whether your
input is current or voltage.
First we recommend you set the
FULL SCALE
calibration ...
Lockout Switch must be OFF
1
2
3
4
5
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
You can now specify the maximum
input signal. Use DIGIT to select each
digit in turn, and the UP or DOWN
arrow to increase or decrease each
digit’s value, as required. eg set
20.0000
if your input is 4-20mA
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Press to accept
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Display now shows
rd Hi
briefly. You
can now specify the maximum reading
and decimal point position. Press Set2
button for 3 seconds to set decimal point
position. Use up and down arrows to
move the decimal point and press OK
when done. Then, use DIGIT to select
each digit in turn, and the UP or DOWN
arrow to increase or decrease each
digit’s value, as required. eg set 100.000
if your display range is 0 to 100.000
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Press to accept
Done!
!!
Defaults are
4-20mA = 0-100.00 for dCA
and
0-10V = 0-100.00 for dC V
Display shows
theor
followed by
dC A
or
dC V
,
depending on
whether you have chosen current or
voltage input, then
In Hi
OFF
Circuit board ON
Set1
Set2
Output
Alarms
Digit
OK
Press 3 seconds
Содержание INTUITIVE INT4-P