Open Contacts
Closed Contacts
Energise
De-energise
Energise
De-energise
Energise
De-energise
Energise
De-energise
Alarm Board Configuration & Adjustment
For failsafe operation (where contacts open on alarm or when power is lost to
the meter) set the jumpers for OPEN CONTACTS and DE-ENERGISE on alarm.
To access to the alarm board, first remove power from meter, including any
power which might be on the alarm output circuitry.
Look on the top and bottom surfaces of the case, near the rear. You will see two
small screws, one on each surface. Remove both screws. Now, clip off the front
bezel and slide the meter assembly carefully out via the front of the case.
The relay board plugs into the main board. Gently separate the two boards.
Select relay output contact
status, when relays are
de-energised (power removed
from meter) by placing these
jumpers...
and set these jumper to make
the alarms energise or de-
energise on trip. De-energise
means you will get an alarm if
power is lost to the meter.
When you have set the jumpers, refit the board to the meter and carefully slide
the assembly back into the case.
Fit the two small board screws to the top and bottom surfaces.
Page 11
AL1
AL2
AL3
AL4