Configuring the UTRED-16 for logging
UTRED-16 User Guide
15
Figure 3:
Alarm ranges and thresholds
Figure 4:
Representation in LogTag
®
Analyzer
You need to observe some basic rules when entering alarm conditions into the
configuration screen in LogTag
®
Analyzer:
l
A primary alarm condition must be entered before the corresponding secondary
alarm condition.
l
Equally, primary and secondary alarm conditions must be entered before the
corresponding tertiary alarm condition.
l
You can enter a different number of upper and lower conditions, or only upper, or
only lower conditions, or none at all.
l
A secondary upper alarm cannot be entered with a lower threshold value than the
primary upper alarm.
l
A tertiary upper alarm cannot be entered with a lower threshold value than the
secondary alarm. Threshold values can, however, be equal and combined with
different time-to-activation values. For example, you can enter a primary upper
alarm with 8 °C threshold and 10 accumulative readings, plus an alarm with 8 °C
threshold and 5 consecutive readings. In this instance the alarm will be triggered, if
either 10 readings in total are above 8 °C, or 5 consecutive readings above 8 °C have
occurred.