LogikaControl LOGIK 26-S Скачать руководство пользователя страница 9

        

 

 

 

Revision 1 – 04.12.2015  

9/28 

 
CONNECTION SERIAL NET RS485 

 

To connect a serial net you have to pay carefully attention to some executive aspects: 

1)

 

Use flexible cable, shielded, twisted 22 AWG type. 

2)

 

Connect D- and D+ to two conductors of same couple and 0 to a third one (if available) or both conductors of a 

second couple. 

3)

 

Connect the cable’s shield to only one end of 0. 

4)

 

DO NOT CONNECT the cable’s shield to the electrical ground of the plant. 

5)

 

The net MUST NOT BE LONGER than 400 meters. 

6)

 

Max connectable units through serial net RS 485 is 32. 

7)

 

In case of connection via serial line RS485 you have to set the parameter 

C08 

into menu 

04

 Compressor setup: 

this is the number you need to combine to the recognition of the controller.  

8)

 

The units on serial net RS485 must be connected without any reversal: pole D+ to D+, pole D- to D-, pole 0 to 0. 

9)

 

In case of connection with more than 2 units it is necessary to provide only one line without any deriving.  

At the terminal both starting and ending the net it is possible to place (in parallel to  D- and D+) a termination 

resistance 120  Ohm.  

In the picture below you can see the connection of 4 units on serial net RS485 by using a shielded cable with two 
twisted couples.   

 

 

 

 

NOTES  ON  THE  WIRING:  wrong  wiring  can  damage  both  the  controller  and  other  devices  connected  to  the 
serial port. 

 

 

WARNINGS TO THE WIRING RS485

 

1)

 

The  cable  must  be  placed  into  a  TRUNK  SEPARATED  by  power  cables  and  any  potentially  dangerous  cables  as 

lighting plant and so on. 

2)

 

DO NOT PLACE signal cables next to power bar, lighting lamps, antennas, transformers; 

3)

 

Keep  signal  cables  FAR  2  METERS  MINIMUM  from  units  with  heavy  inductive  (distribution  cabinet,  motors, 

inverter). 

4)

 

Don’t pull the cables with a strength over 12 Kg; stronger strength can damage the wires and reduce the signal 

transmission on the line. 

5)

 

DO NOT: twist, knot, crush or fray the conductors.  

6)

 

Do not make any joints between lengths of cable:  always use only one cable to connect any single unit to each 

others. Strip the end part carefully, do not crush the cable next to core-hitches or safety supports. 

7)

 

Always respect the position of the colors at the both sides of the connection. 

Once the wiring is complete, visually and physically check the cables are undamaged and properly placed 

 
 

 
 

 

Содержание LOGIK 26-S

Страница 1: ...Revision 1 04 12 2015 1 28 Instructions and Advices to use the electronic controller Logik 26 S ORIGINAL INSTRUCTIONS INDUSTRIAL CONTROL EQUIPMENT 39UG FILE E316817...

Страница 2: ...16 M1 8 INVERTER RS485 DANFOSS 17 M1 9 ANALOG OUTPUT 18 M1 10 HOURS FILTERS OIL 19 M1 11 MAINTENANCE LIST 19 M1 12 ALARMS LIST 19 M1 13 TIMER START STOP 20 M1 14 RESET 20 ALARMS 21 ALARMS WITH IMMEDI...

Страница 3: ...T LOGIKA CONTROL TECHNICAL OFFICE IN CASE OF DOUBT ON THE LAST VERSION ATTENTION LA LOGIK 26 S EST UN CONTROLE EQUIPMENT INDUSTRIEL PAS UN INSTRUMENT DE SECURITE POUR LE FONCTIONNEMENT D UN COMPRESSEU...

Страница 4: ...24Vac to detect IN 1 emergency stop button IN 2 thermal motor IN 3 thermal fan IN 4 remote start stop IN 5 air filter pressure switch IN 6 separator filter differential pressure switch IN 7 settable a...

Страница 5: ...ere must be enough space for wiring and connectors 3 The rear side of the controller must be protected against condensation oil and dust 4 Don t wash the front panel by water injection clean the front...

Страница 6: ...Revision 1 04 12 2015 6 28 ELECTRICAL DRAWING AND LEGEND OF THE CONNECTIONS...

Страница 7: ...5 RL3 star contactor Pole 6 RL2 delta contactor configurable Pole 7 RL1 line contactor Pole 8 common 24 230Vac Terminal M7 Pole 1 IN 7 settable as door of electrical cabinet open control phase relay...

Страница 8: ...onnected before the contact of the relay When the pressure switch opens the auxiliary relay opens power to the digital inputs the controller detects all the digital inputs open and signal the alarm SE...

Страница 9: ...lel to D and D a termination resistance 120 Ohm In the picture below you can see the connection of 4 units on serial net RS485 by using a shielded cable with two twisted couples NOTES ON THE WIRING wr...

Страница 10: ...the data from the inverter are visualized frequency F current I power P and temperature T Data are visualized on the right side 7b or left side 7a according the inverter configuration is on the air e...

Страница 11: ...safety timer I09 Pressure set compressor running unload or stand by I10 Remote start stop input open I11 Compressor running I12 Stop by timer the display visualizes day and time of the next start I13...

Страница 12: ...f the menu you can shift back to the main visualization by pushing for about 5 seconds ANTIPANIC FUNCTION In any label or sub menu related to the setting and or visualizations after 180 seconds from t...

Страница 13: ...sword reset M1 1 INFO This sub menu visualizes the following info 1 Working hours 2 Load hours 3 Load during last 100 working hours updated every 5 hours 4 Frequeny set on output 4 20mA if enabled 5 S...

Страница 14: ...inverter modulating in Master slave operation new SI noth inverter modulating NO master max speed if both units are running 0 2 C08 Compressor Nr 1 32 Enter MODBUS address of the compressor 1 1 C09 S...

Страница 15: ...SLAVE time to switch Master into Slave if the difference of working hours between the two compressors is bigger than the setting of this parameter the unit with more hours will not be Master as long...

Страница 16: ...set 1 or 2 only AP4 is the max internal pressure allowing to run the motor see icon I13 page 11 M1 6 TEMPERATURES In this menu you can change the setting related to the temperature Parameters setting...

Страница 17: ...e 0 00s 99 99s 0 00s 3 DA7 Reset Energy Meter 0 1 0 3 DA8 Jog Ramp Time 0 0s 300 0s 20 0s 3 DA9 PID int mult 0 10 4 00 1 00 3 Setup Drive NOTE If you set the parameter a value different from 0 on the...

Страница 18: ...1 1 PI2 xPM1 SETPOINT FEEDBACK Parameters setting range default and password level are reported in the table below Function Description Setting range Default Press Temp Password level PI1 PID prop gai...

Страница 19: ...HECK COMP is not enabled If parameter C BL is set 29 999 the alarm BEARING LUB is not enabled bearing lubricating By changing the set value than the count in progress is re calculated Example CAF set...

Страница 20: ...vious data Next pushing of the Enter button allows to select hours and minutes of all start stop event visualized When the stop minutes of the last interval of the day are selected by pushing Enter yo...

Страница 21: ...Separator filter differential pressure switch open IN6 ALARMS WITH COMPRESSOR SHUT OFF AFTER 30 SECONDS UNLOAD RUNNING Code Description Cause 26 PRESS TRANSD FAILURE Working pressure transducer failu...

Страница 22: ...tarts hour menu 4 The compressor will not stop and keep on running loading unloading according the pressure till the end of one hour time from the first starting in the same hour 61 ALLARME INVERTER I...

Страница 23: ...5 is over Once the compressor stops for reaching pressure set the timer Wt5 starts during that time if you push the start button the display visualizes and the compressor will not start till the Wt5 c...

Страница 24: ...ou have to delete this filer by cutting the terminal of the resistor R11 Thermoregulation of the fan default RL5 The symbol indicates the fan is on While delta contactor is on air end temperature equa...

Страница 25: ...ommand you can use also relay outputs RL2 RL5 RL6 or RL7 eventually through external relays These outputs have to be set through the parameters C13 C14 C15 and C16 value 5 in case of C18 1 and value 1...

Страница 26: ...working after maintenance only you can restore the Master Slave operation In case of serial connection failure both compressors will be Master MASTER SLAVE INVERTER ONLY FOR LOGIK26S LOGIK33S In case...

Страница 27: ...al wrong electrical wiring or bad assembling can be cause of failures or malfunctioning of the controller in these cases both warranty and own technical features of the controller declines Technical f...

Страница 28: ...Revision 1 04 12 2015 28 28...

Отзывы: