Solenoid valve operation (RL4)  

The symbol 

 indicates the load solenoid valve is ON. 

The unload timer Wt4 can be managed according two different ways settable on C03.

 

1.

 

Wt4 set as fixed timer

: when the pressure reaches stop set, the load solenoid valve (RL4) switches OFF and the timer 

Wt4 starts; once the timer is over, if the pressure is not yet under the start pressure, the compressor stops.  

During  that  timer,  if  the  pressure  goes  down  the  start  set,  the  load  solenoid  valve  (RL4)  switches  in  ON  and  Wt4 

erases.  

2.

 

Wt4 set as variable timer

: at the first start the compressor follow the same cycle repoterd on point 1 above; during the 

next cycle the controller counts time the pressure spent to go from stop set to start set; if this time (

tx

), is bigger the 

Wt4 set, the next Wt4 timer will be shorter (1 minute less) and so on till a minimum time of 2 minutes.  

While 

tx

 will be lower than Wt4 changed, the unload time uploaded will be Wt4 set again. 

ATTENTION

: on the contact of the solenoid valve relay is mounted an RC filter (22 

F + 100 

) sized for a power of 4,7W; 

in case you use a solenoid valve with less power, if the solenoid valve keeps on exciting while the contact is open, you have 

to delete this filer by cutting the terminal of the resistor R11. 

 

Thermoregulation of the fan (default RL5) 

The symbol   indicates the fan is on. 
While delta contactor is on: 

 

air end temperature equal or higher than WT3 = fan ON  

 

air end temperature lower than (WT3 - WT4) = fan OFF  

 

Operation of the condensate drain solenoid valve (default RL6)  

The symbol   indicates the condensate drain is activated. 

During  the  operation of  the  load  solenoid valve  (RL4),  the  condensate drain  solenoid  valve  (RL6)  operates  according  the 

parameters Wt6 and Wt7; besides it is OFF while load solenoid valve is off too.  

 

Compressor status (settable on RL5, RL6 or RL7) 

When the compressor is ON the relay is activated, when the compressor is OFF because the pressure set is reached, the 

relay is OFF.  

 

Compressor start/stop under weekly timer control 

When the compressor is operated by weekly timer, during OFF time the display visualizes the symbol 

 with day and time 

of the next ON; during the operation the same symbol is visualized on the top right corner of the display. 

When the compressor is in operation under timer control you can stop it by  simply pushing the Stop button and you can 

restore it under timer control by pushing Start only. 

When the compressor is stopped by timer you can start it by keeping on pusher the Start button for 5 seconds and you can 

restore it under timer control by pushing the Stop button only. 

 

 
 
 
 
 
 
 
 
 
 

Содержание LOGIK 26-S

Страница 1: ...Revision 1 04 12 2015 1 28 Instructions and Advices to use the electronic controller Logik 26 S ORIGINAL INSTRUCTIONS INDUSTRIAL CONTROL EQUIPMENT 39UG FILE E316817...

Страница 2: ...16 M1 8 INVERTER RS485 DANFOSS 17 M1 9 ANALOG OUTPUT 18 M1 10 HOURS FILTERS OIL 19 M1 11 MAINTENANCE LIST 19 M1 12 ALARMS LIST 19 M1 13 TIMER START STOP 20 M1 14 RESET 20 ALARMS 21 ALARMS WITH IMMEDI...

Страница 3: ...T LOGIKA CONTROL TECHNICAL OFFICE IN CASE OF DOUBT ON THE LAST VERSION ATTENTION LA LOGIK 26 S EST UN CONTROLE EQUIPMENT INDUSTRIEL PAS UN INSTRUMENT DE SECURITE POUR LE FONCTIONNEMENT D UN COMPRESSEU...

Страница 4: ...24Vac to detect IN 1 emergency stop button IN 2 thermal motor IN 3 thermal fan IN 4 remote start stop IN 5 air filter pressure switch IN 6 separator filter differential pressure switch IN 7 settable a...

Страница 5: ...ere must be enough space for wiring and connectors 3 The rear side of the controller must be protected against condensation oil and dust 4 Don t wash the front panel by water injection clean the front...

Страница 6: ...Revision 1 04 12 2015 6 28 ELECTRICAL DRAWING AND LEGEND OF THE CONNECTIONS...

Страница 7: ...5 RL3 star contactor Pole 6 RL2 delta contactor configurable Pole 7 RL1 line contactor Pole 8 common 24 230Vac Terminal M7 Pole 1 IN 7 settable as door of electrical cabinet open control phase relay...

Страница 8: ...onnected before the contact of the relay When the pressure switch opens the auxiliary relay opens power to the digital inputs the controller detects all the digital inputs open and signal the alarm SE...

Страница 9: ...lel to D and D a termination resistance 120 Ohm In the picture below you can see the connection of 4 units on serial net RS485 by using a shielded cable with two twisted couples NOTES ON THE WIRING wr...

Страница 10: ...the data from the inverter are visualized frequency F current I power P and temperature T Data are visualized on the right side 7b or left side 7a according the inverter configuration is on the air e...

Страница 11: ...safety timer I09 Pressure set compressor running unload or stand by I10 Remote start stop input open I11 Compressor running I12 Stop by timer the display visualizes day and time of the next start I13...

Страница 12: ...f the menu you can shift back to the main visualization by pushing for about 5 seconds ANTIPANIC FUNCTION In any label or sub menu related to the setting and or visualizations after 180 seconds from t...

Страница 13: ...sword reset M1 1 INFO This sub menu visualizes the following info 1 Working hours 2 Load hours 3 Load during last 100 working hours updated every 5 hours 4 Frequeny set on output 4 20mA if enabled 5 S...

Страница 14: ...inverter modulating in Master slave operation new SI noth inverter modulating NO master max speed if both units are running 0 2 C08 Compressor Nr 1 32 Enter MODBUS address of the compressor 1 1 C09 S...

Страница 15: ...SLAVE time to switch Master into Slave if the difference of working hours between the two compressors is bigger than the setting of this parameter the unit with more hours will not be Master as long...

Страница 16: ...set 1 or 2 only AP4 is the max internal pressure allowing to run the motor see icon I13 page 11 M1 6 TEMPERATURES In this menu you can change the setting related to the temperature Parameters setting...

Страница 17: ...e 0 00s 99 99s 0 00s 3 DA7 Reset Energy Meter 0 1 0 3 DA8 Jog Ramp Time 0 0s 300 0s 20 0s 3 DA9 PID int mult 0 10 4 00 1 00 3 Setup Drive NOTE If you set the parameter a value different from 0 on the...

Страница 18: ...1 1 PI2 xPM1 SETPOINT FEEDBACK Parameters setting range default and password level are reported in the table below Function Description Setting range Default Press Temp Password level PI1 PID prop gai...

Страница 19: ...HECK COMP is not enabled If parameter C BL is set 29 999 the alarm BEARING LUB is not enabled bearing lubricating By changing the set value than the count in progress is re calculated Example CAF set...

Страница 20: ...vious data Next pushing of the Enter button allows to select hours and minutes of all start stop event visualized When the stop minutes of the last interval of the day are selected by pushing Enter yo...

Страница 21: ...Separator filter differential pressure switch open IN6 ALARMS WITH COMPRESSOR SHUT OFF AFTER 30 SECONDS UNLOAD RUNNING Code Description Cause 26 PRESS TRANSD FAILURE Working pressure transducer failu...

Страница 22: ...tarts hour menu 4 The compressor will not stop and keep on running loading unloading according the pressure till the end of one hour time from the first starting in the same hour 61 ALLARME INVERTER I...

Страница 23: ...5 is over Once the compressor stops for reaching pressure set the timer Wt5 starts during that time if you push the start button the display visualizes and the compressor will not start till the Wt5 c...

Страница 24: ...ou have to delete this filer by cutting the terminal of the resistor R11 Thermoregulation of the fan default RL5 The symbol indicates the fan is on While delta contactor is on air end temperature equa...

Страница 25: ...ommand you can use also relay outputs RL2 RL5 RL6 or RL7 eventually through external relays These outputs have to be set through the parameters C13 C14 C15 and C16 value 5 in case of C18 1 and value 1...

Страница 26: ...working after maintenance only you can restore the Master Slave operation In case of serial connection failure both compressors will be Master MASTER SLAVE INVERTER ONLY FOR LOGIK26S LOGIK33S In case...

Страница 27: ...al wrong electrical wiring or bad assembling can be cause of failures or malfunctioning of the controller in these cases both warranty and own technical features of the controller declines Technical f...

Страница 28: ...Revision 1 04 12 2015 28 28...

Отзывы: