LogikaControl LOGIK 26-S Скачать руководство пользователя страница 14

        

 

 

 

Revision 1 – 04.12.2015  

14/28 

 
M1-4  COMPRESSOR SETUP 

In this menu you can change the general setting of the compressor. 

Parameters, setting range, default and password level are reported in the table below: 

 

Code 

Description 

Value 

Meaning 

Default  Level 

C01 

Restart 

MAN-AUT 

Restart after power off: MAN (manual) – AUT (automatic) 

MAN 

C02 

Starts/hour 

0 ÷ 60 

Starts/hour of the motor allowed 

C03 

Timer Wt4 

SI-NO 

Wt4 operation: YES =  fixed – NO = variable 

YES 

C04 

Control phases 

YES-NO 

Logika control phases uni: 

YES = enabled   -   NO = disabled 

YES 

C05 

Safety 

YES-NO 

Safety operation: 

YES = enabled   -   NO = disabled 

NO 

C06 

Low voltage 

YES-NO 

Alarm low voltage : 

SI = enabled   -   NO = disabled 

YES 

C07 

Multiunit 

operation 

0/1/2/3 

Multiunit options: 

0 = stand alone – 1 = Master/Slave   

2 = Master/Slave new – 3= Multiunit Slave 

C07.1 

Timer Master/Slave 

 

00÷200 h 

 

Balancing working hours: 

in case of setting “00” the balancing is not allowed; Master 

is the compressor with address 1 

100 h. 

C07.2 

Timer slave 

1 ÷ 99 min. 

Slave support: 

After power on if Master unit has not reached stop set until 

the time set in this parameter, the slave starts to support  

5 min. 

C07.3 

Maintenance mode 

YES/NO 

In case of Multiunit Slave, the compressor works on 

standing alone and Multiunit Master is informed this 

compressori s out of order 

NO 

C07.4 

Inverter twin 

YES/NO 

Both inverter modulating in Master/slave operation new 

SI = noth inverter modulating 

NO = master max speed if both units are running 

C08 

Compressor Nr 

1 ÷ 32 

Enter MODBUS address of the compressor 

C09 

Serial number 

15 

alphanumerical  

characters 

Serial number of the compressor 

 

C10 

Flow Air Delivered 

100 / 99990  Capacity: nominal air flow of the compressor (liters/min.) 

1000L/min 

C11 

Input PTC 

YES/NO 

Input PTC configuration: 

NO = disabled – SI = enabled 

C12 

Input IN 7 

0/1/2/3 

Input IN7 configuration: 

0 = disabled – 1 = door open  

2 = control phases relay – 4= high temperature bearings 

C13 

Output RL2 

0÷6 

Relay RL2 setting: 

0=default (star contactor)  

1=fan - 2 = condensate drain  - 3=compressor status 

4=alarm - 5 = motor activated - 6 = load valve on – 

7 = lubricating - 8 = off - 9 = activation on power on for 

the time Wt5  
10 = activation on power on for the time Wt5 and 

activation in case of alarm  

C14 

Output RL5 

0/6 

See C13 

C15 

Output RL6 

0/6 

See C13 

C16 

Output RL7 

0/6 

See C13 

C17 

Shut-off C—h 

NO/YES 

Compressor stop once the timer “Check compressor” is 

over: 

NO = disabled – SI = shut-off alarm 

NO 

C18 

Output 4/20mA 

0/1/2 

Operation output 4/20mA and PID: 

0= disabled  

1 = enabled on working pressure control  

2 = enabled on air end temperature control 

C19 

Aux input 4/20mA  

0÷4 

Configuration auxiliary input 4/20mA: 

0=disabled – 1= relative pressure (delta in relation to the 

working pressure) – 2=power inverter – 3=current inverter 

4=inverter temperature 

C19.1 

Timer separator filter 

1 ÷ 600 sec.  Delay timer separator filter alarm 

30s 

Содержание LOGIK 26-S

Страница 1: ...Revision 1 04 12 2015 1 28 Instructions and Advices to use the electronic controller Logik 26 S ORIGINAL INSTRUCTIONS INDUSTRIAL CONTROL EQUIPMENT 39UG FILE E316817...

Страница 2: ...16 M1 8 INVERTER RS485 DANFOSS 17 M1 9 ANALOG OUTPUT 18 M1 10 HOURS FILTERS OIL 19 M1 11 MAINTENANCE LIST 19 M1 12 ALARMS LIST 19 M1 13 TIMER START STOP 20 M1 14 RESET 20 ALARMS 21 ALARMS WITH IMMEDI...

Страница 3: ...T LOGIKA CONTROL TECHNICAL OFFICE IN CASE OF DOUBT ON THE LAST VERSION ATTENTION LA LOGIK 26 S EST UN CONTROLE EQUIPMENT INDUSTRIEL PAS UN INSTRUMENT DE SECURITE POUR LE FONCTIONNEMENT D UN COMPRESSEU...

Страница 4: ...24Vac to detect IN 1 emergency stop button IN 2 thermal motor IN 3 thermal fan IN 4 remote start stop IN 5 air filter pressure switch IN 6 separator filter differential pressure switch IN 7 settable a...

Страница 5: ...ere must be enough space for wiring and connectors 3 The rear side of the controller must be protected against condensation oil and dust 4 Don t wash the front panel by water injection clean the front...

Страница 6: ...Revision 1 04 12 2015 6 28 ELECTRICAL DRAWING AND LEGEND OF THE CONNECTIONS...

Страница 7: ...5 RL3 star contactor Pole 6 RL2 delta contactor configurable Pole 7 RL1 line contactor Pole 8 common 24 230Vac Terminal M7 Pole 1 IN 7 settable as door of electrical cabinet open control phase relay...

Страница 8: ...onnected before the contact of the relay When the pressure switch opens the auxiliary relay opens power to the digital inputs the controller detects all the digital inputs open and signal the alarm SE...

Страница 9: ...lel to D and D a termination resistance 120 Ohm In the picture below you can see the connection of 4 units on serial net RS485 by using a shielded cable with two twisted couples NOTES ON THE WIRING wr...

Страница 10: ...the data from the inverter are visualized frequency F current I power P and temperature T Data are visualized on the right side 7b or left side 7a according the inverter configuration is on the air e...

Страница 11: ...safety timer I09 Pressure set compressor running unload or stand by I10 Remote start stop input open I11 Compressor running I12 Stop by timer the display visualizes day and time of the next start I13...

Страница 12: ...f the menu you can shift back to the main visualization by pushing for about 5 seconds ANTIPANIC FUNCTION In any label or sub menu related to the setting and or visualizations after 180 seconds from t...

Страница 13: ...sword reset M1 1 INFO This sub menu visualizes the following info 1 Working hours 2 Load hours 3 Load during last 100 working hours updated every 5 hours 4 Frequeny set on output 4 20mA if enabled 5 S...

Страница 14: ...inverter modulating in Master slave operation new SI noth inverter modulating NO master max speed if both units are running 0 2 C08 Compressor Nr 1 32 Enter MODBUS address of the compressor 1 1 C09 S...

Страница 15: ...SLAVE time to switch Master into Slave if the difference of working hours between the two compressors is bigger than the setting of this parameter the unit with more hours will not be Master as long...

Страница 16: ...set 1 or 2 only AP4 is the max internal pressure allowing to run the motor see icon I13 page 11 M1 6 TEMPERATURES In this menu you can change the setting related to the temperature Parameters setting...

Страница 17: ...e 0 00s 99 99s 0 00s 3 DA7 Reset Energy Meter 0 1 0 3 DA8 Jog Ramp Time 0 0s 300 0s 20 0s 3 DA9 PID int mult 0 10 4 00 1 00 3 Setup Drive NOTE If you set the parameter a value different from 0 on the...

Страница 18: ...1 1 PI2 xPM1 SETPOINT FEEDBACK Parameters setting range default and password level are reported in the table below Function Description Setting range Default Press Temp Password level PI1 PID prop gai...

Страница 19: ...HECK COMP is not enabled If parameter C BL is set 29 999 the alarm BEARING LUB is not enabled bearing lubricating By changing the set value than the count in progress is re calculated Example CAF set...

Страница 20: ...vious data Next pushing of the Enter button allows to select hours and minutes of all start stop event visualized When the stop minutes of the last interval of the day are selected by pushing Enter yo...

Страница 21: ...Separator filter differential pressure switch open IN6 ALARMS WITH COMPRESSOR SHUT OFF AFTER 30 SECONDS UNLOAD RUNNING Code Description Cause 26 PRESS TRANSD FAILURE Working pressure transducer failu...

Страница 22: ...tarts hour menu 4 The compressor will not stop and keep on running loading unloading according the pressure till the end of one hour time from the first starting in the same hour 61 ALLARME INVERTER I...

Страница 23: ...5 is over Once the compressor stops for reaching pressure set the timer Wt5 starts during that time if you push the start button the display visualizes and the compressor will not start till the Wt5 c...

Страница 24: ...ou have to delete this filer by cutting the terminal of the resistor R11 Thermoregulation of the fan default RL5 The symbol indicates the fan is on While delta contactor is on air end temperature equa...

Страница 25: ...ommand you can use also relay outputs RL2 RL5 RL6 or RL7 eventually through external relays These outputs have to be set through the parameters C13 C14 C15 and C16 value 5 in case of C18 1 and value 1...

Страница 26: ...working after maintenance only you can restore the Master Slave operation In case of serial connection failure both compressors will be Master MASTER SLAVE INVERTER ONLY FOR LOGIK26S LOGIK33S In case...

Страница 27: ...al wrong electrical wiring or bad assembling can be cause of failures or malfunctioning of the controller in these cases both warranty and own technical features of the controller declines Technical f...

Страница 28: ...Revision 1 04 12 2015 28 28...

Отзывы: