background image

 

Position Light Signals (common cathode wiring; e.g. Oregon Rail Supply) 

Wiring for position light signals is shown in Figure 2 using the Eastbound signal outputs; the connections are similar for the 
Westbound  signal  outputs.  For  common  cathode  LED  signals  you  MUST  use  current  limiting  resistors!  Within  the signal 
head are six or seven LEDs; if you have a B&O style color position light signal then it will not have a center LED and you 
will not use the CTR terminal on the 

Block Animator/2

If you are using the Oregon Rail Supply brand of signals it is 

NOT  necessary  to  purchase  their  diode  logic  board;  the 

Block  Animator/2

  contains  all  of  the  necessary  circuitry  to 

properly  control  these  signals. 

Although  we  include  150  ohm  current  limiting  resistors  with  the 

Block  Animator/2

  you 

might find the signal lights too dim. If so, we recommend changing to a value of 100 ohms (e.g. g 

www.mouser.com

 part 

number 291-100-RC). 

NOTE: if you have an Integrated Signal Systems position light signal you might need to lower 

the resistor to a value of 68 ohms. This is due to the fact that these signals have the LEDs wired in SERIES and thus a 
larger voltage is required to turn on the signal.

 

Common (-)

Clear position

Stop position

Approach position

Center LED/bulb

Current limiting resistors 

(see text)

 

 

Figure 2 – Position light signal 

 

If  your  signal  is  an  “absolute”  type  (that  means  it  has  two  red  LEDs/bulbs  for  the  stop 
position while all others are yellow) then you will have to cut the wire jumper labeled JP8 
for the Eastbound signal shown in Figure 3 on the 

Block Animator/2

 board (jumper JP7 is 

for the Westbound signal). Use a pair of diagonal cutters to make the cut. Be sure that the 
two cut ends no longer touch each other by separating them slightly. Failure to do so won’t 
cause  any  damage  but  it  may  cause  the  center  yellow  LED/bulb  to  illuminate  when  the 
signal is in the stop position. 

  

 

 

Figure 3

 

 

Sensor modes 

The 

Block Animator/2

 supports four different sensor (detector) modes: photocell, between-the-rails infrared, across-the-rails 

infrared, and external detector. When you purchased this product it either came with a photocell, infrared components or 
neither (board only, for use with external detectors). The sensor mode is selected using the switches labeled SEN TYPE and 
SEN POL as depicted in the Table 1 below. 
 

 

 

 

 

  

 

 

 

Photocell 

SEN TYPE – OFF 

SEN POL - OFF

 

Between-the-rails Infrared 

SEN TYPE – ON 

SEN POL - ON

 

Across-the-rails Infrared 

SEN TYPE – ON 

SEN POL - OFF

 

External Detector 

SEN TYPE – OFF 

SEN POL - ON

 

 

 

Table 1 – Sensor mode selection

 

 

Содержание Block Animator/2-CC

Страница 1: ...ow aspect has been added When enabled the signal will transition from yellow to flashing yellow before returning to green This simulates an Approach Medium indication There is no need to swap chips on...

Страница 2: ...ule for illumination is simple the signal shall be illuminated when the preceding block is occupied The Block Animator 2 supports this feature when the APPRL switch is ON CLOSED and works as follows S...

Страница 3: ...d to turn on the signal Common Clear position Stop position Approach position Center LED bulb Current limiting resistors see text Figure 2 Position light signal If your signal is an absolute type that...

Страница 4: ...ator 2 will think the train has actually backed up and exited the block W2 W1 E2 E1 Figure 5 Photocell wiring Photocells require a light source above them to function properly On most layouts the room...

Страница 5: ...IR detector in some plastic or metal tubing You can also recess the IR detector slightly below the ties and roadbed Figure 7a Figure 7b Using Across the rails Infrared With this sensor mode and physi...

Страница 6: ...ch means that when a train is detected the output is pulled to ground When no train is sensed the detector output is an open circuit or floating You will need 3 detection blocks or zones Figure 10 sho...

Страница 7: ...signals will sequence from red yellow flashing yellow green Signal Fade reproduces the behavior of older prototype signals which used bulbs As the indications change the aspects colors will fade off...

Страница 8: ...either of its detector input terminals and the GND terminal AND change the sensor mode to External Detector see Table 1 on page 4 The signal should immediately change to red If not then the Block Ani...

Отзывы: