background image

68 ohms

1/4 watt

Detector

Blue

wire

Black

wire

Emitter

Black

wire

White

wire

 

 

Figure 9 – IR component wiring  

(W1 input shown; replicate for E2, W2 and E1 inputs respectively) 

 

 

Using an external detector 

Use this sensor mode if you’d prefer to use a different type of detector such as an NCE BD20 current sensing detector. Any 
brand of detector should work provided that its output is an open collector, “active low” polarity, which means that when a 
train is detected the output is pulled to ground. When no train is sensed the detector output is an open circuit or “floating.”   
You will need 3 detection blocks or zones. Figure 10 shows how they would be partitioned. 

Signal

EB

Signal

WB

W          E

West approach block

East approach block

Center block

 

 

Figure 10 – External detector block/zone partitioning 

 

 

Figure 11 shows how simple it is to connect the BD20 block detectors to the 

Block Animator

/2.  

 

West 

approach

detector

GND

OUT

Center 

block

detector

GND

OUT

East 

approach

detector

GND

OUT

NCE BD20

GND

2
1

OUT

 

 

Figure 11 – External detector wiring (NCE BD20 shown) 

 

Содержание Block Animator/2-CC

Страница 1: ...ow aspect has been added When enabled the signal will transition from yellow to flashing yellow before returning to green This simulates an Approach Medium indication There is no need to swap chips on...

Страница 2: ...ule for illumination is simple the signal shall be illuminated when the preceding block is occupied The Block Animator 2 supports this feature when the APPRL switch is ON CLOSED and works as follows S...

Страница 3: ...d to turn on the signal Common Clear position Stop position Approach position Center LED bulb Current limiting resistors see text Figure 2 Position light signal If your signal is an absolute type that...

Страница 4: ...ator 2 will think the train has actually backed up and exited the block W2 W1 E2 E1 Figure 5 Photocell wiring Photocells require a light source above them to function properly On most layouts the room...

Страница 5: ...IR detector in some plastic or metal tubing You can also recess the IR detector slightly below the ties and roadbed Figure 7a Figure 7b Using Across the rails Infrared With this sensor mode and physi...

Страница 6: ...ch means that when a train is detected the output is pulled to ground When no train is sensed the detector output is an open circuit or floating You will need 3 detection blocks or zones Figure 10 sho...

Страница 7: ...signals will sequence from red yellow flashing yellow green Signal Fade reproduces the behavior of older prototype signals which used bulbs As the indications change the aspects colors will fade off...

Страница 8: ...either of its detector input terminals and the GND terminal AND change the sensor mode to External Detector see Table 1 on page 4 The signal should immediately change to red If not then the Block Ani...

Отзывы: